Hot Surface - Grundfos AP40 Safety Instructions And Other Important Information

Table of Contents

Advertisement

Pumps cannot be operated with frequency
converter.
DANGER
Electric shock
Death or serious personal injury
Connect the pump to an external main
switch, which ensures all-pole
disconnection with a contact
separation according to EN 60204-1.
It must be possible to lock the main
switch in position 0. Type and
requirements as specified in EN
60204-1.
DANGER
Electric shock
Death or serious personal injury
If the power cable is damaged, it must
be replaced by the manufacturer, his
service agent or a similarly qualified
person.
DANGER
Electric shock
Death or serious personal injury
Before the first startup, check the cable
for visible defects to avoid short
circuits.
Level controllers
The liquid level can be controlled by the Grundfos LC
level controllers.
Suitable level controllers:
LC 231: compact solution with certified motor
protection for single- and dual-pump versions.
LC 241: cabinet solution offering modularity and
customisation for single- and dual-pump versions.
In the following description, "level switches" can be air
bells, float switches or electrodes depending on the
selected pump controller.
Depending on the security levels and the number of
pumps, level switches can be used in the following
setups:
Dry run (optional)
Stop
Start pump 1 (single-pump version)
Start pump 2 (dual-pump version)
High level (optional)
Analogue level transmitters can be used, and all
levels can be customised. Level switches can be
used with level transmitters, for dry-run protection and
high level alarm.
The pump must not run dry. Install an
additional level switch to ensure that the
pump is stopped in case the stop level
switch is not operating.
Installing level switches
When installing the level switches, observe the
following points:
To prevent air intake and vibrations, install the
stop level switch, so the pump is stopped before
the liquid level is lowered to the middle of the
motor housing.
Install the start level switch, so the pump is started
at the required level. The pump must always start
before the liquid level reaches the bottom inlet
pipe.
Always install the high-level alarm switch about 10
cm above the start level switch. However, the
alarm must always be given before the liquid level
reaches the inlet pipe.
For further settings and information, see the
installation and operating instructions for the selected
level controllers.
Startup
Before starting the product:
Make sure that the fuses have been
removed.
Make sure that all protective
equipment has been connected
correctly.
Check the oil level.
Test the insulation resistance.
CAUTION

Hot surface

Minor or moderate personal injury
If the float switches cannot work
properly, dry running of the pump may
cause overheating. Ensure that the
float switches can move freely.
CAUTION
Crushing of hands
Minor or moderate personal injury
Do not put your hands or any tool into
the pump inlet or outlet after the pump
has been connected to the power
supply, unless it has been switched off
by removing the fuses or switching off
the main switch.
Make sure that the power supply
cannot be switched on unintentionally.
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ap50Ap60Ap70

Table of Contents