Si12-796

8. Removal of Shunt

Procedure
Step
1
Remove 6 screws of
the tie wire presser
plate.
Remove 4 screws of
2
the right side panel.
Remove the putty.
3
Before taking this
procedure, make sure
there is no refrigerant gas
left in the refrigerant
pipes.
Disconnect the 5
4
brazed points of the
shunt.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Tie wire pressure plate
Right side panel
Shunt
Putty
Fasten the rubber packing
with double-faced adhesive
tape when mounting.
Rubber
packing
(R2266)
Brazed points
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas welding rod.
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
(R2267)
refrigerant gas is exposed to
open flames, noxious gas
may be generated.)
Removal of Shunt
Points
Caution
Warning
21