Table 13 - Setpoint Screen Parameters - York YSCD Manual

Versecon air conditioning unit
Table of Contents

Advertisement

The parameters in Table 13 can be programmed using the Setpoint screen.
TABLE 13 – SETPOINT SCREEN PARAMETERS
DESCRIPTION
Unit Enable
Min DX Prs Drop (FlexSys units only)
POA DX Prs Drop (FlexSys units only)
AC – S/A Dew En (FlexSys units only)
AC-S/A Dew Min (FlexSys units only)
AC – S/A Dew Max (FlexSys units only)
AC – S/A Dew Dif (FlexSys units only)
AC-S/A Temp En
Econ-S/A Tmp En
AC/Econ-S/A SP
AC-R/A Temp En
Econ-R/A Tmp En
AC/Econ – R/A SP
Heat – S/A Tmp En
Heat S/A Tmp SP
Heat R/A Tmp En
Heat R/A Tmp SP
Fan-VAV/CV En
Fan Sp BAS En (FlexSys units only)
VFD Sp % by BAS (FlexSys units only)
Fan-S/A Pres SP
Static Value
H2O Econ En
O/A Econ En
O/A Damper Min
Cond Valve Min
Econ Valve Min
JOHNSON CONTROLS
OPTIONS
On / Off
0.2 "wc – 1.0"wc
.06"wc to 1.0"wc
ON / OFF
40.0° F – 90.0° F
40.0° F – 90.0° F
2.0° F – 10.0° F
On / Off
On / Off
40° F – 90° F
On / Off
On / Off
40° F – 90° F
On / Off
40° F – 115° F
On / Off
40° F – 90° F
CV /VAV
On / Off
0% to 100%
0.0" wc to 2.0" wc
Low, High, Avg
On / Off
On / Off
0 % - 100 %
0% TO 100%
0% TO 100%
FORM 145.05-NOM2 (807)
DEFAULT VALUE
Off
0.5 "wc
0.1 "wc
On
48.0° F
60.0° F
5.0° F
On
On
55° F
Off
Off
75° F
On
110° F
On
72° F
VAV
Off
0 %
1.0
Avg
On
Off
15%
15%
0%
51
6