Location And Clearances; Rigging And Unit Handling; Table 4 - Access Requirements; Fig. 1 - Recommended Service And Maintenance Clearance - York YSCD Manual

Versecon air conditioning unit
Table of Contents

Advertisement

Installation

LOCATION AND CLEARANCES

The following guidelines should be used to select a
suitable location for the unit installation:
The unit is designed for indoor installation only
Verify the fl oor or foundation is level. For proper
unit operation the unit should be level with a
1/16" side to side and 1/8" front to back. Failure
to level the unit properly could result in conden-
sate management problems, such as standing
water inside the unit.
For installation, service and maintenance access, the
following clearances should be followed. Minimum
clearances required by local, state, or national codes,
such as NEC take precedence over those listed in Figure
1 and Table 4. Clearance is required to allow room for
side fi lter access, mechanical cleaning of the condenser
tubes and water economizer coil, access to expansion
valves and other control components and to allow for
possible fan shaft or compressor removal. Additional
clearance should be considered for component
replacement such as condenser, evaporator, water
economizer coil and supply fan. Even though there is
no vertical clearance specifi cation listed clearance above
the unit may be advantages during change out of any of
the above components.
LEFT
24"
42"
FRONT
RIGHT
24"
FIG. 1 – RECOMMENDED SERVICE AND
MAINTENANCE CLEARANCE
14
TABLE 4 – ACCESS REQUIREMENTS
AREA
UNIT FRONT
UNIT REAR
UNIT LEFT
UNIT RIGHT

RIGGING AND UNIT HANDLING

Units are shipped with a protective covering, which
should remain in place while the unit is being moved
to its fi nal location.
during unloading or moving as this
may result in serious damage.
Unit weights are listed in Table 5 in this manual. These
weights must be referred to when selecting a crane for
rigging. Contact your Johnson Controls Sales Offi ce if
you have any questions regarding unit weights.
18"
BACK
LDO10371
FORM 145.05-NOM2 (807)
DISTANCE
COMPONENT ACCESSED
MOST ELECTRICAL AND POW-
ER COMPONENTS, VFD, FAN
BELT ADJUSTMENTS, GREAS-
42"
ING BOTH BEARINGS, FAN
WHEEL, FAN MOTOR, SHAFT
PULL, ETC.
FILTER ACCESS, COIL ACCESS,
18"
ETC.
24"
24"
Never allow any part of the unit to fall
Ensure lifting equipment capacity
exceeds unit weight by an adequate
safety factor to prevent injury, death,
or unit damage.
JOHNSON CONTROLS