___________________________________________________________________________________ CONTENTS Contents………………………………………………………..2 1. Description of products & features………………………….3 2. Specification…………………………………………………...6 3. Dimensions…………………………………………………..21 4. Pipe and wiring installation…..……………………………..26 5. PCB photo, wiring diagram and function description……..72 6. Diagnostic code and troubleshooting.……………………...95 7. Outdoor performance curves………..……………………..101 8. Indoor air velocity and temperature distribution curves..105 9.
___________________________________________________________________________________ 1.Description of products & features 1.1. Brief Introduction for T1,T2,T3 working condition Climate type Type Conditioner Cooling Only 18 ℃~43℃ 10℃~35℃ 21℃~52℃ Heat pump -7℃~43℃ -7℃~35℃ -7℃~52℃ Electricity Heating ~43℃ ~35℃ ~52℃ 1.2 Operating Range of Air Conditioners Working temperature range Rated Maximum Minimum...
Page 4
___________________________________________________________________________________ 1.3 Product features DC inverter technology, high energy efficiency, higher EER A+, energy saving for the user The outdoor unit adopts DC inverter compressor and motor, so save power energy is just to save money for the user. And the outdoor can match with multiple indoor units, up to 5 sets. Even when you have already installed the air conditioner, if you want to add or reduce one unit, go ahead freely as long as your operation complies with our design.
Page 5
___________________________________________________________________________________ on the operation panel. Then according to the failure code chart, you can eliminate the failure soon. Central control function, if connected with a central controller That is convenient for building management. Weekly timing function, if connected with a weekly timer Universal power supply for 50Hz and 60Hz The multi upgrade series adopts universal power supply for 50Hz and 60Hz, which is convenient for design.
___________________________________________________________________________________ 2. Specifications Item Model YJU3YH019BAR-A-X Function Cooling Heating Rating capacity 5400 6500 Power input (indoor + outdoor) 1410 1520 Current input (indoor + outdoor) 6.13 EER / COP 3.84 4.28 Minimum capacity 1500 1800 Minimum power input Maximum capacity 7000 8100 Maximum power input (indoor + outdoor)
Page 7
___________________________________________________________________________________ Item Model YJU4YH025BAR-A-X Function Cooling Heating Rating capacity 7600 8600 Power input (indoor + outdoor) 2100 2060 Current input (indoor + outdoor) EER / COP 3.62 4.18 Minimum capacity 1500 1800 Minimum power input Maximum capacity 9000 9500 Maximum power input (indoor + outdoor) 3500 3500 Power source...
Page 8
___________________________________________________________________________________ Item Model YJU4YH030BAR-A-X Function Cooling Heating Rating capacity 8100 9800 Power input (indoor + outdoor) 2220 2430 Current input (indoor + outdoor) 10.6 EER / COP 3.65 4.03 Minimum capacity 1500 1800 Minimum power input Maximum capacity 9800 10500 Maximum power input (indoor + outdoor) 3800 3800...
Page 9
___________________________________________________________________________________ Item Model YJU5YH034BAR-A-X Function Cooling Heating Rating capacity 10000 10700 Power input (indoor + outdoor) 2940 2850 Current input (indoor + outdoor) 12.8 12.4 EER / COP 3.75 Minimum capacity 1500 1800 Minimum power input Maximum capacity 11000 11500 Maximum power input (indoor + outdoor) 4000 4000...
Page 10
___________________________________________________________________________________ Item Model YHKMXH009BARR-FX Function cooling heating Capacity Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 Speed(H-M-L) 690/620/560 r/min Fan motor output power 0.03 Air-flow(H-M-L) m³/h 620/520/450 Type / Diameter inner grooved pipe/φ7...
Page 11
___________________________________________________________________________________ Item Model YHDMXH009BARR-FX Function cooling heating Capacity Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 Speed(H-M-L) 1000/900/800±50 r/min Fan motor output power 0.05 Air-flow(H-M-L) m³/h 550/450/400 Static pressure Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area 0.11...
Page 12
___________________________________________________________________________________ Item Model YHKMXH012BARR-FX Function cooling heating Capacity 3.5(0.9--4.5) 3.7(1.0--4.8) Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 Speed(H-M-L) r/min 690/620/560 Fan motor output power 0.03 Air-flow(H-M-L) 620/520/450 m³/h Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area m²...
Page 13
___________________________________________________________________________________ Item Model YHFMXH012BARR-FX Function cooling heating Capacity 3.5(0.9--4.5) 3.9(1.0--4.8) Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX2 Speed(H-M-L) r/min 1100/1025/825 Fan motor output power 0.09 Air-flow(H-M-L) m³/h 650/550/450 Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area 0.20...
Page 14
___________________________________________________________________________________ Item Model YHDMXH012BARR-FX Function cooling heating Capacity 3.5(0.9--4.5) 4.0(1.0--4.8) Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 1000/900/800±50 Speed(H-M-L) r/min Fan motor output powe 0.05 Air-flow(H-M-L) 550/450/400 m³/h Static pressure Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area...
Page 15
___________________________________________________________________________________ Item Model YHKMXH018BARR-FX Function cooling heating Capacity 5.0(1.8--5.8) 5.2(2.0--6.5) Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 Speed(H-M-L) 795/690/550±50 r/min Fan motor output power 0.065 Air-flow(H-M-L) 680/620/500 m³/h Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area m²...
Page 16
___________________________________________________________________________________ Item Model YHFMXH018BARR-FX Function cooling heating Capacity 5.0(1.8--5.8) 5.5(2.0--6.5) Sensible heat ratio 0.71 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX2 Speed(H-M-L) r/min 1220/1190/1050 Fan motor output power 0.075 Air-flow(H-M-L) 800/720/650 m³/h Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area 0.45...
Page 17
___________________________________________________________________________________ Item Model YHDMXH018BARR-FX Function cooling heating Capacity 5.0(1.8--6.0) 5.5(2.0--6.2) Sensible heat ratio 0.73 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX2 Speed(H-M-L) 730±30/540±30/400±30 r/min Fan motor output pow 0.05 Air-flow(H-M-L) 850/780/600 m³/h Static pressure Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area...
Page 18
___________________________________________________________________________________ Item Model YHKMXH024BARR-FX Function cooling heating Capacity 6.5(2.0--7.3) 7.1(2.5--8.0) Sensible heat ratio 0.72 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX1 Speed(H-M-L) 670±40/550±50/460±50 r/min Fan motor output power 0.16 Air-flow(H-M-L) 1300/1100/870 m³/h Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area m²...
Page 19
___________________________________________________________________________________ Item Model YHFMXH024BARR-FX Function cooling heating Capacity 6.3(2.0--7.3) 7.1(2.5--8.0) Sensible heat ratio 0.72 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX2 Speed(H-M-L) 1220±40/1190±50/1050±50/980±50 r/min Fan motor output power 0.10 Air-flow(H-M-L) m³/h 800/720/650 Type / Diameter inner grooved pipe/φ7 Heat exchanger Total Area 0.49...
Page 20
___________________________________________________________________________________ Item Model YHDMXH024BARR-FX Function cooling heating Capacity 6.8(2.0--7.6) 7.1(3.0--8.3) Sensible heat ratio 0.72 Dehumidifying capacity 10‐³×m³/h Power Supply 1PH,220-230V 50-60HZ Type × Number CENTRIFUGALX2 Speed(H-M-L) 1250±40/1130±40/1000±50/850±50 r/min Fan motor output power 0.05 Air-flow(H-M-L) 1200/1050/850(white terminal 0 Pa) m³/h Static pressure Type / Diameter inner grooved pipe/φ7 Heat exchanger...
___________________________________________________________________________________ 3. Dimension YJU3YH019BARRA-X Air inlet Air inlet Air outlet Handle Handle Liquid pipe:Ø6.35(flared)1/4 A unit connection Gas pipe :Ø9.52(flared)3/8 Liquid pipe:Ø6.35(flared)1/4 B unit connection Gas pipe :Ø9.52(flared)3/8 Liquid pipe:Ø6.35(flared)1/4 C unit connection Gas pipe :Ø9.52(flared)3/8 YJU4YH025/30BARRA-X Air inlet Gas pipe Ø9.52(flared) 3/8(A,B,C unit) Ø12.7(flared) 1/2(D unit) Air inlet...
Page 22
___________________________________________________________________________________ YJU5YH034BARRA-X Air inlet Air inlet Gas pipe Air outlet Ø9.52(flared) 3/8(A,B,C,D unit) Ø12.7(flared) 1/2(E unit) Handle Indoor and outdoor Handle connect wiring hole (30*48) Handle A unit connection B unit connection C unit connection D unit connection E unit connection Liquid pipe Ø6.35(flared) 1/4 ___________________________________________________________________________________...
___________________________________________________________________________________ 4. Pipe and wiring installation 4.1 Multi combination and the data YJU3YH019BAR-A-X combination and the data COOLING total cooling total power input total current Combinatio capacity(Kw) capacity(kW) (kW) (A)@230V (W/W) (Nom. cooling) energy Comb. min. rate min. rated max. min.
Page 27
___________________________________________________________________________________ COOLING Rated capacity Output/kW total cooling total power input total current Combinations (Nom. cooling) capacity(kW) (kW) (A)@230V (W/W) energy Comb. rated label Unit Unit Unit Unit Unit Unit Unit Unit min. rated min. rated max. min. rated max. capaci data data data...
Page 28
___________________________________________________________________________________ YJU4YH025BARR-A-X combination and the data HEATING Rated capacity Output/kW total heating total power input total current Combinations (Nom. heating) capacity(KW) (A)@230V (W/W) energy Comb. rated label Unit Unit Unit Unit Unit Unit Unit Unit min. rated min. rated max. min.
Page 29
___________________________________________________________________________________ YJU4YH030BARR-A-X combination and the data COOLING energy Rated capacity Output/kW total cooling total power input total current Combinations label capacity(kW) (kW) (A)@230V (Nom. cooling) (W/W) Comb. min. rated max. min. rated max. min. rated max. Unit Unit Unit Unit Unit Unit Unit...
Page 30
___________________________________________________________________________________ HEATING total heating total power input total current energy Rated capacity Output/kW Combinations label capacity(KW) (A)@230V (Nom. heating) (W/W) Comb. Unit Unit Unit Unit Unit Unit Unit Unit min. rated max. min. rated max. min. rated max. rated data data data data...
Page 31
___________________________________________________________________________________ YJU5YH034BARR-A-X combination and the data COOLING Rated capacity Output/kW total cooling total power input total current Combinations (Nom. cooling) capacity(kW) (kW) (A)@230V (W/W) energ Comb. rated y label Unit Unit Unit Unit Unit Unit min. rated max. min. rated max.
___________________________________________________________________________________ 4.2. Wiring connection YJU3YH019BARRA-X If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm2 Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other. ___________________________________________________________________________________ -34-...
Page 35
___________________________________________________________________________________ YJU4YH025/30BARRA-X If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm2 Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other. ___________________________________________________________________________________ -35-...
Page 36
___________________________________________________________________________________ YJU5YH034BARRA-X If this outdoor unit connects with AS*S1ERA, the connecting cable is 1.5mm2 Connect the connecting wires between indoor and outdoor units and ensure the sequence numbers on terminals match with each other. ___________________________________________________________________________________ -36-...
Page 37
___________________________________________________________________________________ 4.3 Limitation values on pipe installation YJU3YH019BARRA-X Item Unit Description Standard Maximum A,B,C liquid pipe mm Size of the liquid side connection pipe φ6.35 A,B,C Gas pipe mm Size of the gas side connection pipe φ9.52 L1 (one way) Max.piping length between IU and OU of the way ≤10 ≤25...
Page 38
___________________________________________________________________________________ YJU4YH025/30BARRA-X Item Unit Description Standard Maximum A,B,C, Dliquid pipe mm Size of the liquid side connection pipe φ6.35 A,B,C Gas pipe mm Size of the gas side connection pipe φ9.52 D Gas pi[pe mm Size of the gas side connection pipe φ12.7 L1 (one way) Max.piping length between IU and OU of the way...
Page 39
___________________________________________________________________________________ YJU5YH034BARRA-X U n i Item Description Standard Maximum A,B,C,D,E liquid pipe mm Size of the liquid side connection pipe φ6.35 A,B,C,D Gas pipe mm Size of the gas side connection pipe φ9.52 E Gas pi[pe mm Size of the gas side connection pipe φ12.7 L1 (one way) Max.piping length between IU and OU of the way...
Page 40
___________________________________________________________________________________ Connection cautions model YJU3YH019BARRA-X YJU4YH025/30BARRA-X YJU5YH034BARRA-X connection priority between indoor and stop valve higher from down to up when there is 1 indoor,the prior stop valve is when there are 2 indoors,the prior D、C C、B E、D stop valves are when there are 3 indoors,the prior D、C、B...
Page 41
___________________________________________________________________________________ 4.4 Outdoor installation Installation figure please refers to YJU4YH025BAR-A-X Arrangement of piping directions Rear left Rear right Left Right Below Attention must be Wrap the insulation pipe with the finishing tape paid to the rising from bottom to top. up of drain hose Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no...
___________________________________________________________________________________ Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed. In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts.(Prepare four sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.) It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.
Page 44
___________________________________________________________________________________ 3. Refrigerant piping work 1). Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the tor wrenches. Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas. Flare nut fightening torque Flare nut for 6.35...
Page 45
___________________________________________________________________________________ 5. Refilling the refrigerant Check the type of refrigerant to be used on the machine namiplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.(It should have something like "liquid filling siphon attached"...
Page 46
___________________________________________________________________________________ 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipe. Inter unit wiring Wall Be sure to Gas pipe place a cap. Liquid pipe Rain If no flare cap is available, cover the flare mouth with tape Liquid pipe Gas pipe to keep dirt or water...
Page 47
___________________________________________________________________________________ In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve caps from liquid stop valve and gas stop valve. 2) Carry out forced cooling operation. liquid 3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench. stop valve Hexagonal 4) After two to three minutes, close the gas stop vaile and stop forced cooling...
Page 48
___________________________________________________________________________________ Wire cover A Wire cover C Terminal block Wire cover A Wire cover C Wire cover D Wire cover B Wire cover E Wire cover B Terminal block Valve cover Valve cover –¨ 25.40 4. Wiring method of indoor unit Loosen wire cover and connect the power line and communication wire of indoor unit to the terminal correspondingly.
Page 49
___________________________________________________________________________________ Before starting the test running, please confirm the following works have been done successfully. 1) Correct piping work; 2) Correct wiring work; 3) Correct match of indoor and outdoor unit; 4) Proper recharge of refrigerant if needed. Make sure that all the stop valves are fully open. Check the voltage supplied to the outdoor and indoor units, please cinfirm that is 230V.
___________________________________________________________________________________ 4.6. Convertible type Floor console SELECTING THE MOUNTING POSITION Fig.A may be difference WARNING 1.5m Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall Left Right CAUTION...
Page 56
___________________________________________________________________________________ PREPARING INDOOR UNIT INSTALLATION REMOVE THE INTAKE GRILL Open the intake grill and remove the three or four or six screws.(Fig. 1) Fig. 1 Remark: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order.
Page 57
___________________________________________________________________________________ 2. INSTALLING DRAIN HOSE Wrap the insulation (drain hose) around the drain Select whether the drain hose will be connected hose connection. (Fig.7) to the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.
Page 58
___________________________________________________________________________________ 1. DRILLING FOR PIPING 3. INSTALLING BRACKETS Select piping and drain directions. Install the brackets with nuts, washers and spring (Fig.11) washers.(Fig. 15) Rear (Install the drain Fig. 15 hose in the direction.) Right Spring washer Bracket Special nut Fig.
___________________________________________________________________________________ 5. INSTALL THE DRAIN HOSE OUTDOOR UNIT INSTALLATION Select whether the drain hose will be connected to CONNECTING THE PIPING the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure 1. FLARE PROCESSING the drain hose with a nylon fastener.(Fig.6) (1) Cut the connection pipe with pipe cutters so Wrap the insulation (drain hose)around the drain that the pipe is not deformed.
Page 60
___________________________________________________________________________________ 3. PIPING CONNECTION Fit the nut on and fasten 90 0.5 The maximum length and drop height of connecting pipe Please refer to the installation manual of outdoor unit Joint To ensure the efficiency , Pipes shall be as short as possible. Spanner Cautions for piping connection Do not twist or deform the connecting pipe.
___________________________________________________________________________________ HOW TO CONNECT WIRING TO THE TERMINALS A. For solid core wiring (or F-cable)(Fig.24A) (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire. (2) Using a screwdriver, remove the terminal screw(s) on the terminal board. (3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
___________________________________________________________________________________ ELECTRICAL WIRING (2) Pull out the electric component box. CAUTION Fig.28 (1) Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts. (2) Connect the connection cords firmly to the terminal block.
___________________________________________________________________________________ ELECTRICAL WIRING (2) OUTDOOR UNIT (1) Is there any abnormal noise and vibration during WARNING operation? (1) Always use a special branch circuit and install a special (2) Will noise, wind, or drain water from the unit disturb receptacle to supply power to the room air conditioner. the neighbors? (2) Use a circuit breaker and receptacle matched to (3) Is there any gas leakage?
Page 64
___________________________________________________________________________________ 2. Mount the cover plate.(Left) (1) Join the cover plate (left) and mount with screws. Fig. 33 3. Mount the intake grill. (1) Cut the right side of the intake grill. This is only when the pipe exits from the right side Fig.
___________________________________________________________________________________ 5. Installation procedure 1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See Figure 1) 2.
Page 67
___________________________________________________________________________________ The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is white), the distance between air duct outlet and air conditioner outlet is no more than 0.5m;...
Page 68
___________________________________________________________________________________ 2. Installation of air return duct Use rivets to connect the air return duct to the air return inlet of the indoor unit. The other end connects to the air return shutter. as shown in Fig.2. air return air return shutter duct indoor unit...
Page 69
___________________________________________________________________________________ Original concrete slab Use hole hinge, hole plunger or hole bolt. Steel reinforcement structure Use steel angle or new support steel angle directly. Hanging bolt Support steel angle Suspension screw Hanging of the indoor unit Fasten the nut on the suspension screw and then hang the suspension screw in the Tslot of the suspension part of the unit.
Page 70
___________________________________________________________________________________ Pipe and insulation material Pipe Rigid PVC pipe VP31.5mm (internal diameter) Insulation Foamed PE with thickness above 7mm Hose Drain pipe size: ? 19.05mm (3/4") PVC pipe. The hose is used for adjusting the off-center and angle of the rigid PVC pipe. Directly stretch the hose to install without making any deformation.
___________________________________________________________________________________ Pipe expansion dimensions as follows: Incorrect Correct Pipe diameter Size A (mm) 6.35 mm (1/4 " ) 0.8 ~ 1.5 9.52 mm (3/8 " ) 1.0 ~ 1.8 Slope Damage Bur Partial Overlong 12.7 mm (1/2 " ) 1.2 ~ 2.0 Pipe expander The connection of indoor unit pipes must use double spanners.
Page 72
___________________________________________________________________________________ Brazed seam B=8.0-9.0(mm) d=4.3-5.3(mm) Ring Terminal T=1.0-2.0(mm) (For your referrence) Wiring method of ring terminal 2 Wiring method of straight terminal For connecting line which end is not a ring, its wiring method as follows: loosen wiring screw ans insert the end of connecting line totally into the terminal block,then tighten the screw and pull the connecting line slightly to confirm that it is clamped firmly.
Page 77
___________________________________________________________________________________ 5.1.3 . Switch setting and functions: Outdoor main PCB 0151800075 SW5 definition definition cooling only heat pump (default) set ON if frost easily set OFF if hard to frost(default) Max. running current is 11A normal control (default) OFF ON --- 3U19* ON ON --- 4U25*...
Page 78
___________________________________________________________________________________ 3. Main control functions 3.1 Refrigerant diagram Pipe system for YJU3YH019BARRA-X ___________________________________________________________________________________ -77-...
Page 79
___________________________________________________________________________________ Pipe system for YJU4YH025/30BARRA-X ___________________________________________________________________________________ -78-...
Page 80
___________________________________________________________________________________ Pipe system for YJU5YH034BARRA-X 3.2 Outdoor frequency control 3.2.1 Compressor running frequency range: 20~95RPS 3.2.2 Defination of high-efficiency operation and its frequency control In order to meet the cooling request at high ambient temperature and the heating request at low ambient temperature, we set the high-efficiency operation.
Page 81
___________________________________________________________________________________ 3.3.2 Initialization of EEV EEV driving speed: open direction: 32MS; close direction: 32MS 3.3.3 Open angle limitation of EEV Unit stop Adjustable upper Thermostat ON Thermostat Adjustable lower limitation limitation 5(E) 450(E) Cool/dry standard open 5(E) 80(E) angle+tolerance heat 60(E)...
Page 82
___________________________________________________________________________________ not go down greatly. Ambient temp. TA≤27degree, when compressor stops, the electric heater will be electrified. When TA≥32degree, or compressor running, the electric heater will be off. Heater ON Ambient temp. TA(℃) 3.6 Control of defrosting in heating In heating mode, defrosting temp. sensor will check the frosting condition of outdoor heat exchanger and make defrosting control.
Page 83
___________________________________________________________________________________ 3.6.4 Defrosting operation flow chart beginning fixed frequency indicated FQY 60s defrosting FQY 80 Hz(E) soft startup compressor outdoor motor send defrosting signal to indoor Auto 4-way valve 450-pulse 450-pulse 350-pulse(E) all EEVs auto open angle auto open angle all indoor motors ON anti-cold air function 3.7Frequency control when Td is too high...
Page 84
___________________________________________________________________________________ 3.8 Frequency control when there is CT over current protection Stop immediately, if abnormal stop 3 times in 1 hour, the unit will stop and alarm. 1.0 I Reduce FQY rapidly 2HZ/S 0.95I Reduce FQY rapidly 1HZ/S 0.93I Reduce FQY slowly 1HZ/10S 0.90I Remain FQY 0.88I...
Page 85
___________________________________________________________________________________ ·When unit stops, the reason that system still checks the low pressure : in a long time stop, make protection for the compressor on the condition of great refrigerant leakage. ·The reason that low pressure switch action time is 30 seconds: when compressor stops, low pressure does not change, so it will be shorter than the set time in operation.
Page 86
___________________________________________________________________________________ 3.11 Oil return operation control 3.11.1 Entering condition When the compressor running frequency is lower than 58Hz (E) continuously for 8 hrs, the system will enter oil return operation. In the course of mode changeover, manual unit stop or protective unit stop, the time will be accumulative.
Page 87
___________________________________________________________________________________ After oil return in cooling mode, the quit condition of refrigerant eliminated: 1 minute later after oil return is over Td Tc & ‐ >30℃ Ts Tc2AVE ‐ >30℃ Tc2AVE< 35 ‐ ℃ Max. 10 minutes Oil return procedure in heating mode: Send oil return signal oil return begins oil return over...
Page 88
___________________________________________________________________________________ 5.2 Indoor unit 5.2.1 Indoor unit PCB photo ___________________________________________________________________________________ -87-...
Page 92
___________________________________________________________________________________ 6.4 In AUTO mode, when the indoor unit occurs abnormal operation, the indoor unit will keep OFF state, and the buzzer will not sound until the outdoor mode and the requested mode of indoor unit are the same. 6.5 COOL (included AUTO COOL), DRY, FAN are not abnormal mode. 6.6 HEAT and FAN are not abnormal mode.
Page 93
___________________________________________________________________________________ 12. Water pump control 12.1 Water pump will be electrified when indoor unit enters non-heating mode until indoor unit stops. 5 minutes later after indoor unit stops, water pump will stop. 12.2 When indoor unit is in heating mode, water pump will not operate. 12.3 In OFF state and in any mode, once float switch signal is measured, indoor unit will send OFF signal to outdoor and send the failure code of drainage system to the wired controller, then the water pump will work until the float switch signal is cancelled.
Page 94
___________________________________________________________________________________ 17. Healthy negative ion function When receiving the healthy signal from the wired controller or remote controller, if fan motor is running, the negative ion will work; If the fan motor stops, the negative ion generator will stop. 18. Auto-restart function 18.1 Wired control type: jumper J07 at high level, auto-restart is available, if at low level, auto-restart is cancelled;...
Page 95
___________________________________________________________________________________ 20. Setting method of temperature compensation Tcomp A. Wired control type unit: this function is not available B. Remote control type unit: In cooling or heating mode, there is always with the temp. compensation. In heating mode: In 24℃ heating mode, press SLEEP(or SWING) button 7 times continuously within 5 seconds, indoor buzzer sounds twice, that shows temp.
___________________________________________________________________________________ 6. Diagnostic code and trouble shooting 6.1.1. Diagnostic code for outdoor unit ___________________________________________________________________________________ -95-...
Page 97
___________________________________________________________________________________ 6.1.2. Diagnostic code for indoor unit ___________________________________________________________________________________ -96-...
___________________________________________________________________________________ 6.2. Trouble Shooting: Trouble 1: No display on the operation panel start check if display replace display panel and the panel and check unit matched again well if the red diode if the power check the terminal and green diode terminal block is block and the on indoor PCB...
Page 99
___________________________________________________________________________________ Trouble 3: Communication failure between indoor and outdoor start as per the wiring re-wiring, and diagram, check if check again communication wiring is correct check if the if the power cable and the PCB is faulty, communication port communication wire are replace and connecting to the too close, resulting in the...
Page 100
___________________________________________________________________________________ Trouble 8: Outdoor unit alarms sensor failure start as per the wiring re-fix the diagram, check if sensor and connection port check again between sensor and PCB is correct check if the sensor check if the replace sensor is in open circuit or sensor resistor and check the connection port...
Page 101
___________________________________________________________________________________ Failure 11: Low pressure switch failure Reason: 1. Too low system pressure causes that the unit stops and the compressor protection works, the failure can be resumed. 2. Pressure switch wire is not fixed well or in open circuit. start check if the connector check if the 2...
___________________________________________________________________________________ 8. Indoor air velocity and temperature distribution curves 8.1 YHKMXH009-024BARR-FX a. Cooling / Air Velocity Distribution Cooling Blowy angle:40 Air Velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:40 Temperature Distribution 2.7m ___________________________________________________________________________________ -105-...
Page 107
___________________________________________________________________________________ c. Heating / Air Velocity Distribution Heating Blowy angle:70 Air velocity Distribution 2.7m 1.5m/s 1.5m/s 1.0m/s 1.0m/s 0.5m/s 0.5m/s d. Heating / Temperature Distribution Heating Blowy angle:70 Temperature Distribution 2.7m ___________________________________________________________________________________ -106-...
Page 108
___________________________________________________________________________________ 8.2 YHFMXH012-018BARR-FX a) Grounding a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 0.5m/s 1.0m/s 1.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution ___________________________________________________________________________________ -107-...
Page 109
___________________________________________________________________________________ c. Heating / Air Velocity Distribution Heating Blowy angle:5 Air velocity Distribution 0.5m/s 1.0m/s d. Heating / Temperature Distribution Heating Blowy angle:5 Temperature Distribution ___________________________________________________________________________________ -108-...
Page 110
___________________________________________________________________________________ b) Ceiling a. Cooling / Air Velocity Distribution Cooling Blowy angle:25 Air Velocity Distribution 1.0m/s 0.5m/s b. Cooling / Temperature Distribution Cooling Blowy angle:25 Temperature Distribution ___________________________________________________________________________________ -109-...
Page 111
___________________________________________________________________________________ c. Heating / Air Velocity Distribution Heating Blowy angle:65 Air velocity Distribution d. Heating / Temperature Distribution Heating Blowy angle:65 Temperature Distribution ___________________________________________________________________________________ -110-...
___________________________________________________________________________________ 10. Noise level a. Casset type indoor unit .7/ V`nodib dggpnom\o`@ .8/ V`nodib ^ji_dodji@ \4 Wido mpiidib di oc` ijhdi\g ^ji_dodji ]4 V`no di oc` n`hd3\i`^cjd^ ^c\h]`m ^4 Pjdn` g`q`g q\md`n amjh oc` \^op\g a\^ojmn np^c \n mjjh nomp^opm`2 `o^4 Test method According to the testing illustrator, the microphones wearing sponge style cover should be placed in the right position...
Page 117
___________________________________________________________________________________ b. Convertible type indoor unit Test method According to the testing illustrator, the microphones wearing sponge style cover should be placed in the right position ___________________________________________________________________________________ -116-...
Page 120
___________________________________________________________________________________ c. Duct type indoor unit Test method According to the testing illustrator, the microphones wearing sponge style cover should be placed in the right position ___________________________________________________________________________________ -119-...
Page 123
___________________________________________________________________________________ Test method Set the unit: 1) the unit is placed on the rubber whose thickness is 5mm; 2) if the height between the air outlet and ground is less than 1m, block the unit up to 1m.far from ground Test position: After setting the unit ,the test position for the noise is 1m far from the front panel ___________________________________________________________________________________...
___________________________________________________________________________________ 12. Controller functions Base Operation Remote controller SPEED 1. Unit start Press ON/OFF on the remote controller, unit starts. 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT 3.Select temp.setting Press button TEMP-...
___________________________________________________________________________________ Sleep Operation In AUTO mode The unit operaters in corresponding sleep mode Before going to bed,you can simply press the SLEEP adapted to the automatically selected operation button and unit will operate in SLEEP mode and bring mode. you a sound sleep. 4.
Page 131
___________________________________________________________________________________ Timer On/Off On-Off Operation Set clock correctly before starting TIMER operation. 1.After unit starts, select your desired operation mode. 2.Press TIMER button to change TIMER mode. Every time the button is pressed, display changes as follows: Remote controller: BLANK TIMER ON TIMER OFF TIMER ON-OFF...
Page 132
___________________________________________________________________________________ Wired controller Fan speed switch Mode switch Change wind speed Choose running mode Swing switch Open and close air flap Health switch Used to control oxygen TEMP switch function and negative ion Used for changing set temperature MODE SWING MODE CENTRAL Time switch...
Page 133
___________________________________________________________________________________ ON/OFF operation Press ON/OFF switch on line controller directly The line controller displays the running state in the latest time (timing and swing state may not be displayed). MODE SWING 1. Press "ON/OFF" switch. MODE The air conditioner starts operating, and the light on the OPERATION TEMP HEALTH...
Page 134
___________________________________________________________________________________ Present time setting The timing is based on the real time. Thus, the real time should be regulated in advance. The clock regulation steps are as follows: 1.Press "CLOCK" switch "CLOCK" flickers, and the time displayed is the real time. MODE SWING MODE...
Page 135
___________________________________________________________________________________ Timing setting OFF timing: when a set time has elapsed, the unit stops running. ON timing: when a set time has elapsed, the unit starts. Press "ON/OFF"switch firstly, and set up operation mode. Please regulate the clock in advance before using the MODE SWING timing function.
Page 136
___________________________________________________________________________________ Query indoor malfunction history: In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals).
___________________________________________________________________________________ Installation Manual For Wire Controller 1. Take down wire controller from the holder 2. Install the controller holder According to the position of 2 screw holes on the Wire controller holder, drill 2 holes on the wall, and strike the wood 52¡...