Connecting Dc Power - Siemens RUGGEDCOM RS8000H Installation Manual

Rugged ethernet switches
Hide thumbs Also See for RUGGEDCOM RS8000H:
Table of Contents

Advertisement

4.
2.4.2

Connecting DC Power

To connect a high or low DC power supply to the device, do the following:
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
RUGGEDCOM RS8000H
Installation Manual, 12/2021, C79000-G8976-1022-06
Using a #6 ring tongue and #6-32 screw, secure the ground terminal on the
power source to the chassis ground terminal on the device. Make sure the lug is
tightened to 1.7 N·m (15 lbf·in).
1
Stainless Steel Stud
1
#6-32 Screw
2
#6 Ring Tongue
3
Figure 2.7
Chassis Ground Connection
NOTICE
2
3
Installing the Device
2.4.2 Connecting DC Power
15

Advertisement

Table of Contents
loading

Table of Contents