Technical Characteristics - Carrier 30PA Installation, Operation And Maintenance Instructions

Ductable air-cooled scroll chillers and heat pumps
Table of Contents

Advertisement

Ductable air-cooled scroll
chillers and heat pumps
5. T
ECHNICAL CHARACTERISTICS
STD version
30PA/PH
Net cooling capacity
Net power input
Cooling
capacities
Net effi ciency
Seasonal effi ciency
Net heating capacity
Net power input
Net effi ciency
Heating
Seasonal effi ciency
capacities
Average climate
Seasonal effi ciency
Warmer climate
Nominal air fl ow (m
Available static pressure (mm.w.c.)
Outdoor
Number / turbines
circuit
centrifugal
Motor output (kW)
fan
Power input (kW)
Speed (r.p.m.)
Nominal water fl ow (m
Pressure drop (m.w.c.)
Minimum water fl ow (m
Indoor
circuit
Maximum water fl ow (m
Type of hydraulic connections
Diameter of connections
Type
Number of compressors / stages / circuits
Compressor
Oil type
Volume of oil (l)
Type
Global warming potential (GWP)
Refrigerant
Charge (kg)
Environment impact (tCO
Electrical power supply
Electrical
characteristics
Power supply
Compressor (A)
Maximum
Fan (A)
absorbed
Control (A)
current
Total (A)
Length (mm)
Dimensions
Width (mm)
Height (mm)
Empty (kg)
Weight
In operation (kg)
Cooling capacity calculated in accordance with the EN-14511-2013 standard given for outlet water temperature conditions of 7ºC and 35ºC
Heating capacity calculated in accordance with the
Total power input by compressor, motorised fan and electronic control under nominal conditions, calculated in accordance with the
included.
European Seasonal Energy Effi ciency Ratio (ESEER) obtained in accordance with the calculation conditions established by the certifi cation body EUROVENT.

Values
calculated in accordance with the

Energy-effi cient motors IE2.

Climatic warming potential of a kilogram of fl uorinated greenhouse gas in relation to a kilogram of carbon dioxide over a period of 100 years.
(kW)
(kW)
EER
ESEER
(kW)
(kW)
COP
SCOP
ŋs Heat
Prated (kW)
SCOP
ŋs Heat
Prated (kW)
/h)
3
/h)
3
/h)
3
/h)
3
Copeland 3MAF 32 cST, Danfoss POE 160 SZ, ICI Emkarate RL 32 CF, Mobil EAL Artic 22 CC
e)
2
EN-14511-2013
standard given for outlet water temperature conditions of 45ºC and 6ºC WB outdoor temperature.
EN-14825-2013
standard given for
90STD
100STD
17,
21,10
7,75
9,15
2,29
2,31
2,61
2,59
21,80
26,10
7,31
8,90
2,97
2,94
3,11
3,12
121%
122%
16,77
19,19
3,59
3,63
140%
142%
12,73
14,70
6500
7000
2,2
2,2
1,46
1,77
973
1027
3,1
3,7
2,3
3,2
2,2
2,7
6,2
7,4
Gas threaded
1 1/4" M
3,0
3,3
5,9
6,1
12,3
12,7
400 V / III ph / 50 Hz (±10%)
3 Wires + Ground + Neutral
15,2
17,3
5,0
5,0
0,9
0,9
21,1
23,2
1117
860
1447
302
310
306
315
bivalente temperature of -5ºC in average climate and 2ºC in warmer climate.
120STD
160STD
25,20
32,70
10,00
12,60
2,51
2,60
2,81
2,94
29,70
38,30
9,90
12,90
3,00
2,97
3,07
2,95
120%
115%
21,82
26,33
3,57
3,42
140%
134%
16,72
24,30
10000
12200
20
1
3,0
4,0
2,33
2,83
837
734
4,3
5,7
2,9
4,7
3,1
4,1
8,8
11,3
1 1/2" M
Scroll
1 / 1 / 1
3,3
3,3
R-410A
2.088
6,6
6,9
13,8
14,4
20,5
25,4
6,9
8,9
0,9
0,9
28,3
35,2
1398
860
1727
372
390
379
397
outdoor
temperature.
EN-14511-2013
standard. Options are not
180STD
36,00
14,40
2,49
2,85
42,60
14,20
3,01
2,95
115%
31,31
3,35
131%
27,32
12200
4,0
2,83
734
6,2
2,9
4,3
12,7
6,2
7,6
15,9
30,5
8,9
0,9
40,3
388
396
7