Introduction; Operation Limits - Carrier 30PA Installation, Operation And Maintenance Instructions

Ductable air-cooled scroll chillers and heat pumps
Table of Contents

Advertisement

Ductable air-cooled scroll
chillers and heat pumps
1. I
NTRODUCTION
The 30PA/PH cooling only and reversible heat pumps are compact
outdoor air/water units.
Available in two versions:
• STD (Standard)
• HEE (High Energy Effi ciency)
These units have been made for operation indoors in the production
of hot and/or cold water, applicable to heating, cooling, and industry.
They are equipped with centrifugal fan (STD version) or electronic plug-
fan (HEE version), plate exchanger, hermetic scroll compressor, and
electronic control with microprocessor, components optimised for the
R-410A refrigerant.
This range is also offered with an integrated circulation pump:
30PAC/PHC.
The entire range also has the option to include a desuperheater circuit
that allows for the production of hot water at a temperature greater than
in the condensation circuits.
2. O
PERATION LIMITS
Cooling mode
Air
Water
Series
(outlet T.)
Max.
Min.
Max.
30PA/PAC
46ºC 12ºC
18ºC 5ºC
30PH/PHC
46ºC 12ºC
18ºC 5ºC
With control of the condensation pressure operating up to -15ºC.
Minimum outlet temperature. With the option of glycol water for lower
temperature operation from 5ºC to -7ºC.
Heating mode
Air
Water
(outlet T.)
Min.
Max.
Min.
Max.
Min.
--
--
--
20ºC DB -15ºC DB 55ºC
30ºC
• 30PA/PAC
Air-cooled water chillers.
• 30PH/PHC
Reversible heat pump units for operation in negative outdoor
temperatures (greater than -15ºC WB) for water heating and cooling.
Defrosting by reversing the cycle.
After manufacturing, all units are charged with refrigerant and
are tested at the factory, verifying the correct operation of all their
components within the operating range for which they are intended.
The units comply with European Directives: Machinery 2006/42/EC -
EMC 2014/30/EU - LVD 2014/35/EU - PED 2014/68/EC (Category 2)
- RoHS 2011/65/EU - Eco-design 2009/125/CE - Eco-labelling 2010/30/
EU; and with Harmonised Standard: EN 378-2:2012.
Those in charge of the installation, commissioning, operation and
maintenance of the unit must know the instructions contained in this
brochure and the specifi c technical characteristics of the installation place.
+46
+12
--
-15
Mandatory glycol
-7
0
+5
Outlet water temp. in the evaporator °C
+20
+10
+0
-10
-15
+18
+30
+45
+50
Outlet water temp. in the condenser °C
+55
5