American Standard PFWF071A93ABA Installation Manual page 48

Oil fired water boiler with three pass cast iron heat exchanger
Table of Contents

Advertisement

8. Place the bulb of the new manual reset water
temperature limit along with the existing adjustable
supply water thermostat and thermometer gauge
bulbs in the boiler temperature well and secure with
a spring clip. See Figure 61.
9. Route the capillary tube of the manual reset water
temperature limit with the other capillary tubes,
dress neatly and secure with new cable ties. See
Figure 62.
18-CG03D1-4
48
Figure 61
Figure 62
10. Tighten the strain relief cable clamp with a
screwdriver. See Figure 63.
Figure 63
11. Replace the strain relief access panel, close and
secure the control box, and replace the front and
top boiler panels. Restore power and check out limit
switch operation per boiler installation instructions.
See Figure 64.
Figure 64