American Standard PFWF071A93ABA Installation Manual page 47

Oil fired water boiler with three pass cast iron heat exchanger
Table of Contents

Advertisement

4. Center the reset button in the hole and secure
with a locking nut. Use needle nose pliers. See
Figure 57.
5. Replace the reset button cover on the new manual
reset water temperature limit switch. See Figure 58.
Figure 58
Figure 57
6. Attach the wires removed earlier from the auto-
reset water temperature limit to the new manual
water temperature limit. See Figure 59.
Figure 59
7. Carefully unroll the capillary tube of the new
manual reset water temperature limit and feed the
sensing bulb through the strain relief clamp. See
Figure 60.
Figure 60
18-CG03D1-4
47