9.11 Checking boiler efficiency

Carry out performance checks at the intervals
anticipated by the regulations in force.
• Connect a flue analyser to the flue gas anal-
ysis outlets on the flue gas exhaust on the
boiler Figure 9.15.
Flue gas analy-
Figure 9.15
• Make sure that the room thermostat is in the
"heat request" position.
• Draw off an abundant amount of DHW by
opening the taps.
• Activate the "chimney sweep function" at
maximum output in heating mode (see "Set-
ting the boiler's chimney sweep function" on
page 72)
• Check the boiler combustion using the out-
lets located on the flue pipes (Figure 9.15)
and compare the data measured with the
following.
Model M300V.2025 SM
Nominal heat input
Nominal efficiency
Combustion efficiency
Air index
Composition of CO2 fumes
Composition of O2 fumes
Composition of CO fumes
Flue gas temperature
Values refer to tests with 80 mm 1 + 1 m twin pipe
discharge and Methane gas G20 and with heating
delivery/return temperature of 60°/80°C
Figure 9.16
MAINTENANCE
sis outlets
kW
21,0
%
98,4
%
98,7
n
1,3
%
8,5 - 9,5
%
4,8
ppm
220
°C
78
Model M300V.2530 SM
Nominal heat input
Nominal efficiency
Combustion efficiency
Air index
Composition of CO2 fumes
Composition of O2 fumes
Composition of CO fumes
Flue gas temperature
Values refer to tests with 80 mm 1 + 1 m twin pipe
discharge and Methane gas G20 and with heating
delivery/return temperature of 60°/80°C
Figure 9.17
Model M300V.3035 SM
Nominal heat input
Nominal efficiency
Combustion efficiency
Air index
Composition of CO2 fumes
Composition of O2 fumes
Composition of CO fumes
Flue gas temperature
Values refer to tests with 80 mm 1 + 1 m twin pipe
discharge and Methane gas G20 and with heating
delivery/return temperature of 60°/80°C
Figure 9.18
9.12 Checking the condensate dis-
charge siphon
The condensate discharge siphon 32 (Figure
9.19) does not require particular maintenance.
Simply check:
• that solid deposits have not formed and re-
move them if necessary.
• that the condensate outlet pipes are not ob-
structed.
To clean the inside of the siphon, simply re-
move it and turn it upside down so that any
impurities can be extracted.
kW
26,0
%
98,6
%
98,8
n
1,3
%
8,5 - 9,5
%
4,8
ppm
190
°C
78
kW
31,0
%
98,8
%
99,0
n
1,7
%
8,5 - 9,5
%
4,8
ppm
200
°C
78