12
13
Figure 7.3
Figure 7.4
• Scroll through the various menus by press-
ing the keys 13 (back) or 15 (forward), until
Ch5 (Chimney sweep) appears on the LCD
display (Figure 7.5).
• Press the 14 key for 1 second to enter the se-
lected menu.
Figure 7.5
• The letters LP, alternating with the minimum
heating water temperature (e.g.45), appear
on the screen indicating the activation of the
"chimney sweep function" at minimum pow-
er (Figure 7.6).
CHECKING THE GAS SETTINGS
17
16
15
14
Figure 7.6
• Compare the value of CO
gas analyser with the one in the "Data in DHW
mode" table and the values of CO
section "Technical data M300V.2025 SM" on
page 26, "Technical data M300V.2530 SM"
page 30 and "Technical data M300V.3035
SM" page 34.
Check maximum burner pressure
• Press button 15 3 times until the LCD display
indicates the letters dP (chimney sweep ac-
tive in maximum DHW mode) that alternate
with the value of the heating water tempera-
ture (e.g.60), indicating the activation of the
"chimney sweep function" at maximum out-
put in DHW mode (Figure 7.7).
Figure 7.7
• Compare the value of CO
gas analyser with the CO
read on the flue
2
at Q.min.
2
read on the flue
2
value at Q.nom in
2
- 61 -