WIRING DIRECTIONS
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS OR SENSORS.
Each WattStopper BZ series power pack
can supply power for 5 UT-300 sensors.
When using more sensors than this,
multiple power packs are required.
Refer to the wiring diagram on the next
page for the following procedures:
Connect the low voltage:
•RED wire (+24VDC) from power pack
to the +24V terminal on the sensor.
•BLACK wire (Return) from power
pack to Common terminal on the
sensor.
•BLUE wire from power pack to
Control Out terminal on sensor.
To add a MANUAL SWITCH such as the LVS-1 Momentary Toggle Switch, or RS2-3
Low Voltage Momentary Switch to the above applications–connect:
•Wire from one side of switch to +24V terminal on sensor.
•Wire from other side of switch to Man Switch terminal on sensor.
Wiring the ISOLATED RELAY: (The Isolated Relay is rated for 1A@30VAC/VDC)
Connect the wires necessary to the application that requires this output:
•Relay Common (must be used for proper operation)
•N.O. (Normally Open)–Closed when occupancy is detected
•N.C. (Normally Closed)–Open when occupancy is detected