8. STARTUP & ADJUSTMENT (con't)
5.The factory cut-out (pump off) setting is 60 psig. When
the pump reaches 60 psig, the Well-X1
pump off. Check the plumbing for leaks and repair
before continuing. If during startup the cut-out setting
of 60 psig cannot be reached, read the adjustment
instructions to lower the cut-out within the pump's
capability.
6. Slowly open the service valve to allow the system to
pressurize. The pressure may drop slightly during this
process. After the valve is fully open, open the fixture
closest to the Well-X1
to begin drawing water from
the tank.
7. When the system reaches the factory cut-in (pump on)
setting of 40 psig, the pump will start. Like a traditional
mechanical switch, the pressure will begin to rise,
repeating the cycle. If desired, the Well-X1
can now be adjusted as shown below.
will shut the
OPEN CLOSEST
FIXTURE TO
DRAW WATER
settings
10
OPEN SERVICE VALVE
TO PRESSURIZE SYSTEM