Amtrol WELL-X-TROL WX-401 Sizing Instructions

Amtrol WELL-X-TROL WX-401 Sizing Instructions

Potable water well tank

Advertisement

Quick Links

Series 420 & 447
This handbook will discuss the basic sizing used
for our larger Well-X-Trol
440, and 450 series. This allows you to use the Well-
X-Trol
"principle of separation of air and water" on
®
larger jobs that are beyond the typical residential
range.
The Well-X-Trol
models we'll be working with in
®
this handbook are listed in Table 1.
The design features of these larger models allow
us to apply them more creatively than the smaller
residential models found in the Well-X-Trol
200, and 250 series.
The Larger Well-X-Trol
for Maximum Acceptance on Each Operating
Cycle
In the smaller residential Well-X-Trol
is for basic intermittent use and for the usually
found in residential applications. Standard pressure
ranges of (20) PSIG (between pump cut-in and
pump cut-out) are used.
In these applications, full use of the maximum
acceptance volume of the Well-X-Trol
required to meet job conditions.
1400 Division Road, West Warwick, RI 02893
Pressure Switch
s such as WX-400, 420,
®
100,
®
s are Designed and Built
®
s, the design
®
is rarely
®
SIZING INSTRUCTIONS
WELL-X-TROL
POTABLE WATER WELL TANK
T: 401.884.6300
Tab le 1.
WX Model No.
WX Model
NON-CODE
No.
(NON-AS ME )
COD E
(ASM E)
WX-401
WX-401-C
WX–402
WX–402-C
WX-403
WX-403-C
WX-404
WX-404-C
WX-405
WX-405-C
WX-406
WX-406-C
WX-407
WX-407-C
WX-421
Not available
WX-422
Not available
WX-423
Not available
WX-424
Not available
Not available
WX-426
WX-427
Not available
WX-447
WX-447-C
WX-448
WX-448-C
WX-449
WX-449-C
WX-450
WX-450-C
WX-451
WX-451-C
WX-452
WX-452-C
WX-453
WX-453-C
WX-454
WX-454-C
WX-455
WX-455-C
WX-456
WX-456-C
WX-457
WX-457-C
Based on 30 PS IG p re-charge (P
F: 401.885.2567
www.amtrol.com
Total
Maximum
Volume
Acce ptance
(Gallons)
Volume
(Gallons)
17.5
11.25
25
11.25
34
11.25
68
34
90
34
110
34
132
46
158
103
211
137
264
172
317
206
422
274
528
343
53
34
80
52
106
69
132
86
158
102
211
136
264
170
317
205
370
239
422
273
528
341
)
1
®
Maximum
Acce ptance
Factor
(MAF )
.65
.45
.33
.50
.39
.31
.35
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65
.65

Advertisement

loading

Summary of Contents for Amtrol WELL-X-TROL WX-401

  • Page 1 SIZING INSTRUCTIONS WELL-X-TROL ® POTABLE WATER WELL TANK 1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com Tab le 1. WX Model No. WX Model Total Maximum Maximum NON-CODE Volume Acce ptance Acce ptance (NON-AS ME )
  • Page 2 Utilizing the Maximum Capacity of Full Step One – Determine the Best Operating Pressure Range – Pump Cut-In (P2) to Acceptance Well-X-Trol s Series 400, ® Pump Cut-Out (P3): 420, 440 and 450 When used with conventional pressure ranges, these Well-X-Trol models use only a fraction of GROUND LEVEL their maximum capacity.
  • Page 3 For example, if we look at a typical pump curve for We must select a minimum pressure at the Well- a (15) HP – (85) GPM submersible pump – we can X-Trol location that will insure enough pressure ® select a pump cut-in and cut-out point on the curve to keep water flow under pressure at the top of the which will provide optimum pump operation.
  • Page 4 Subtracting the feet of head required for lift (240′) Even though the pump may be rated as a (85) we can convert this point to PSIG: GPM pump (as in our example) the actual capacity in GPM will vary as the pump operates throughout Maximum pump cut-out = 420 feet its pressure range from pump cut-in (30 PSIG) and...
  • Page 5 Step Three: Calculate Acceptance Step Six: Select Well-X-Trol Model that ® Factor (AF) is Equal to or Greater Than “T ”. Remember our formula for calculating the If ASME construction is not required, select from acceptance factor (AF) for diaphragm tanks? 420 series, Table 1.
  • Page 6 NOTES...
  • Page 7 NOTES...
  • Page 8 1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com AMTROL, AMTROL logo and WELL-X-TROL are registered trademarks of AMTROL Inc. and affiliates in the U.S. and elsewhere. All rights reserved. Part #: 9017-102 (04/11) MC# 10005...

This manual is also suitable for:

Well-x-trol wx-402Well-x-trol wx-403Well-x-trol wx-404Well-x-trol wx-405Well-x-trol wx-406Well-x-trol wx-407 ... Show all