Flame inspection window
Clean the flame inspection window (Fig. 47).
Burner
Check for excess wear or loose screws in the mechanisms con-
trolling the air damper and the gas butterfly valve.
Also make sure that the screws securing the electrical leads in the
burner connections are fully tightened.
Clean the outside of the burner, taking special care with the linkag-
es joints and cam.
Gas leaks
Make sure that there are no gas leaks on the pipework between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
6.2.4

Flame presence check

The burner is fitted with an ionisation system which ensures that a
flame is present. The minimum current for plant operation is 3 μA.
The burner provides a much higher current, so that controls are not
normally required.
However, if it is necessary to measure the ionisation current, there
are two methods:
 Flame presence check with RFGO function
Check the level of the flame detection signal with the "Check
mode" function from the flame control: the LEDs from 2 to 6 in-
dicate the flame signal level, respectively. See "LED indicator
and special function" on page 37.
Check Mode
With burner flame on:
hold the reset button on the flame control pressed for at least
3 sec.;
the button colour will change from green to yellow;
each operating status signalling LED will be compared to 20%
of the maximum brightness;
press the reset button again (<0.5 sec) to reset the standard
operation of the signalling LEDs.Safety components.
 Flame presence check with microamperometer instru-
ment
disconnect the plug-socket 24)(Fig. 4, page 11) on the ionisa-
tion probe cable and insert a direct current microamperometer
with a base scale of 100 μA.
Carefully check polarities!
WARNING
Maintenance
6.2.5

Safety components

The safety components must be replaced at the end of their life cy-
cle indicated in Tab. G. The specified life cycles do not refer to the
warranty terms indicated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
35
GB
D709
Fig. 47
20156526
μ A
-
+
Fig. 48
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000
pressurised cycles
10 years or 500,000 start-ups
Tab. G
20160742