Flame Presence Check; Safety Components - Riello RS 28/M Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Fan
Check to make sure that no dust has accumulated inside the fan or
on its blades, as this condition will cause a reduction in the air flow
rate and provoke polluting combustion.
Burner
Check that the graduated sector that controls the air damper is se-
cured by the nut 2)(Fig. 31, page 27).
The tightness of the screws that fasten the cables to the burner ter-
minal strip must also be checked.
Clean the outside of the burner.
Clean and grease the cam variable profile.
Boiler
Clean the boiler as indicated in its accompanying instructions in or-
der to maintain all the original combustion characteristics intact, es-
pecially the flue gas temperature and combustion chamber
pressure.
Gas leaks
Make sure that there are no gas leaks on the pipework between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Flame inspection window
Clean the flame inspection window (Fig. 34).
6.2.4

Flame presence check

The burner is fitted with an ionisation system which ensures that a
flame is present. The minimum current for plant operation is 3 μA.
The burner provides a much higher current, so that controls are not
normally required.
However, if it is necessary to measure the ionisation current, there
are two methods:
 Flame presence check with RFGO function
Check the level of the flame detection signal with the "Check
mode" function from the flame control: the LEDs from 2 to 6 in-
dicate the flame signal level, respectively. See "LED indicator
and special function" on page 32.
Check Mode
With burner flame on:
hold the reset button on the flame control pressed for at least
3 sec.;
the button colour will change from green to yellow;
each operating status signalling LED will be compared to 20%
of the maximum brightness;
press the reset button again (<0.5 sec) to reset the standard
operation of the signalling LEDs.Safety components.
 Flame presence check with microamperometer instru-
ment
disconnect the plug-socket 7)(Fig. 4, page 10) on the ionisation
probe cable and insert a direct current microamperometer with
a base scale of 100 μA.
Carefully check polarities!
WARNING
20154169
Maintenance
6.2.5

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty
terms indicated in the delivery or payment condi-
tions.
WARNING
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
30
GB
D484
Fig. 34
20156526
μ A
-
+
Fig. 35
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000
pressurised cycles
10 years or 500,000 start-ups
Tab. M