Preparation instructions
Numerical line differential protection SIPROTEC 7SD600 V3.0
An overview of the factory settings for the binary in
puts is provided in table 5.2.
Table 5.2
Factory set binary inputs
4th operating level
MARSHALLING
61 MARSH BI 1
61 MARSH BI 2
61 MARSH BI 3
5.5.3

Marshalling of signal relay - block 62

The device has 3 signal outputs (signal relays). As
signment of signal relay SR 1 is fixed with the indica
tion "Protection ready". This indication appears when
the self-monitoring of the device has not detected
any faults.
The other signal relays SR 2 and SR 3 can be marshal
led in block 62. You can reach the block from the in
itial state of the device in level 1 as follows: Press the
B key (forwards), switch to the 2nd operating level
with the " key (next level), scroll with the B key
until block 60 appears on the display. Switch to opera
ting level 3 with the " key and scroll to block 62 with
the B key !: Marshalling signal relay. Selection is
carried out as described in section 5.5.1. Multiple in
dications are permitted, i.e. a logical indication can be
transmitted to several signal relays (see section
5.5.1).
A
6 2
R O U T
B
S R
Use the " key to go to the first signal relay:
A
6 2
R O U T
B
S R 2
5 - 24
5th operating level
BINARY INPUTS
6 1
B I 1
1
> D I F b l k
6 1
B I 2
1
> R e s . L O
6 1
B I 3
1
> R e s. L E D
System manual
Order no. E50417-G1176-C069-A1
Fno.
Comment
Block heading
3003
Blocking of DIF protective function
3008
Reset Lockout function
5
Reset LED
Table 5.3 shows a list of all the signal functions with
their respective function numbers Fno. Signal func
tions have no effect if the relevant protective function
of the device is not available or has been configured
so that it is not available.
The general diagrams in appendix A show the assign
ment of the signal relays on delivery. The following
boxes show some examples of these. Table 5.4 con
tains a complete list of all presettings.
Notes regarding table 5.3. The indications starting
with ">" are direct feedback information of the bi
nary input and have identical status to the binary in
put. They appear as long as the relevant binary input
is actuated.
For further information on the indications, see section
6.4.
[6200]
Beginning of the block "Marshalling of signal relays"
"
[6222]
Marshalling for signal relay 2:
"