Configuring The Functional Scope Of The Device - Block 00 - Siemens SIPROTEC 7SD600 System Manual

Numerical line differential protection
Hide thumbs Also See for SIPROTEC 7SD600:
Table of Contents

Advertisement

Numerical line differential protection SIPROTEC 7SD600 V3.0
"No" key N, the change entered since the E key was
last pressed is canceled and the old value or text is
displayed. This enables you to cancel any erroneous
changes. To continue to scroll forward, you must now
press the relevant arrow key again.
When the setting of a configuration parameter is ter
minated by pressing the enter key E, the associated
data are permanently saved and protected against
power failure in EEPROMs.
Using the A keys (back one level), you can switch
back to the 2nd operating level and move to the next
operating block with B (forwards) or, by pressing the
A key again, you can switch to the first operating le
vel.
A
0 0
C O N
B
Pilot wire monitoring:
0 0
PW . MON
A
E X I S T .
+
NON .
EXIST .
Siemens AG January 1999
Preparation instructions
System manual
5.4.2
Configuring the functional scope of the
device - block 00
The available protective and additional functions can
be configured as EXISTent or NON EXISTent. It is
even possible to select more than one alternative for
some functions.
Functions which have been configured as
NON EXISTent will not be processed in the 7SD600.
There will be no indications and the associated setting
parameters (functions, threshold values) will not be
queried during setting (see section 6.3). In contrast,
the switching off of a function means that the func
tion will be processed, that indications will be genera
ted (e.g. "... switched off"), but that the function will
not affect the overall protection system (e.g. no trip
command).
The following boxes show the options for maximum
configuration of the device. In practice, functions
which are not available will not be displayed.
[7800]
Beginning of the block "Configuring functional scope"
"
[7816]
B
available
not available
5
Order no. E50417-G1176-C069-A1