Wiring diagram for level switch NRS 2-51 .....................12 Key ...............................12 Supply voltage connection ........................13 Connecting the output contacts ......................13 Connecting the level electrode/level transmitter ..................13 Connecting the actual value output ......................13 Tools ..............................13 NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Page 3
Checking the function of the MIN/MAX output contacts ...............22 Passwort protection ..........................23 Troubleshooting Indications, diagnosis and remedies ......................24 Further information Action against high-frequency interference ...................25 Replacing/taking the equipment out of service ..................25 Disposal ..............................25 NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
7-segment LED display. In the event of a malfunction, the MIN and MAX alarm is triggered. If faults occur only in the NRS 2-50, NRS 2-51 level switch, the MIN and MAX alarm is triggered and the system is restarted.
Directives and standards VdTÜV Bulletin “Wasserstand 100” (Water Level 100) The NRS 2-50, NRS 2-51 level switch, in combination with the NRG 2.-.. level electrode and NRGT 26-. level transmitter, has type approval in accordance with VdTÜV Bulletin “Wasserstand 100” (Water Level 100), which describes the requirements for water level control and limiting equip- ment for boilers.
12 VDC Outputs: NRS 2-50, NRS 2-51: 2 volt-free relay contacts, 8 A 250 V AC / 30 V DC cos ϕ = 1. Off delay 3 seconds (MIN/MAX alarm, adjustable switchpoint). NRS 2-51: 1 volt-free relay contact, 8 A 250 V AC / 30 V DC cos ϕ = 1.
Name plate, bottom Actual value output Fuse, Connection of provided level electrode/ on site level transmitter Power consumption Supply voltage Type approval number Disposal info Serial number Fig. 2 NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
The advantage of using the adapter is that the status is visible and alarms can be tested without open- ing the control cabinet door. When installed, the adapter has a rating of IP65. Please refer to the panel adapter Installation & Operating Manual 850625-xx for further information. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Support rail TH 35, EN 60715 Installation in a control cabinet The NRS 2-50, NRS 2-51 level switch is clipped onto a type TH 35, EN 60715 support rail in the control cabinet. Fig. 1 4 NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Max. three NRS/NRR 2-5.. units can be connected (series connection). Central earthing point (CEP) in control cabinet MIN output contact, off delay 3 seconds MAX output contact, off delay 3 seconds Actual value output 4-20 mA NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Max. three NRS/NRR 2-5.. units can be connected (series connection). Central earthing point (CEP) in control cabinet MIN output contact, off delay 3 seconds MAX output contact, off delay 3 seconds Pump output contact Actual value output 4-20 mA NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
EN 60730-1 or DIN EN 60950 between the current loop and live parts of the equipment that are not supplied with safety extra-low voltage (SELV). Attention Do not use unused terminals as support terminals. Tools Screwdriver size 3.5 x 100 mm, fully insulated to VDE 0680-1. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
In the system: Wiring the level electrode/transmitter Connecting the level electrode/level transmitter The NRS 2-50, NRS 2-51 level switch can be combined in a circuit with the NRG 21-.. and NRG 26-21 level electrodes and the NRGT 26-. level transmitter.
Release the terminal strip on the right and left sides, by turning the screwdriver in the direction of the arrow. Remove the terminal strip. Fig. 4 When your changes are complete: Put on the lower terminal strip. Switch the supply voltage back on. The equipment restarts NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Page 16
Please pay attention to the NRGT 26-. Installation & Operating Manual when doing this. Do not change the settings of switches S1 and S4 on code switch NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
E.006 Error Level electrode/transmitter defective, measuring voltage/current too high E.012 Error Lower and upper ends of measuring range wrong way round E.013 Error MIN switchpoint higher than MAX switchpoint NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Please convert the measuring range into percent! Attention When connecting the NRGT 26-. level transmitter, please set the upper and lower end of the measuring range only in the transmitter. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Or after 30s, the actual value is displayed automatically. If password protection is enabled, you must enter the password before you can change parameters. For the password, see page 23. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
100% of the measuring range. CAL.P can be adjusted e.g. 25%. between 25 and 100%. Note Adjusting the measuring range: The advantage of option 2 is that the tank only has to be partially filled. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
MAX LED flashes red Off delay in progress. Water level at or above MAX Delay time elapsed, MAX output contacts 21/23 level switchpoint. MAX LED lights up red closed, 22/23 open. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Turn the rotary knob until the actual value is displayed. Or after 30s, the actual value is displayed automatically. Note The actual value is shown on the 7-segment display. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Disabled password protection is re-enabled after 30 minutes with no activity (rotary knob). The password must be entered again. When the equipment is restarted, the parameters are password-protected, if password protection was previously enabled. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
In the event of a malfunction in the level switch, the MIN and MAX alarm is triggered and the equipment restarts. If the process is continually repeated, the equipment must be replaced. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
In the event of malfunctions or faults that cannot be remedied with the aid of this Installation & Operat- ing Manual, please contact our service centre or authorised agent in your country. NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Page 26
For your notes NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Page 27
For your notes NRS 2-50, NRS 2-51 - Installation & Operating Manual - 819179-05...
Page 28