Functional elements and dimensions ......................15 Installing the NRS 1-56 level switch ......................16 Electrical connection safety notes ....................... 16 Wiring diagram for the NRS 1-56 level switch .................... 17 Electrical connection ............................ 18 Connecting the 24 V DC power supply ..................... 18 Connecting the output contacts........................
Page 3
Action against high-frequency interference ....................28 What to do in the event of system malfunctions..................29 Taking out of service ............................ 29 Disposal ................................ 29 Returning decontaminated equipment ......................29 EU Declaration of Conformity ........................30 NRS 1-56 - Installation & Operating Manual - 850142-00...
How to use this Manual This Installation & Operating Manual describes the correct use of the NRS 1-56 level switch. It applies to persons who integrate this equipment in control systems, install, bring into service, operate, maintain and dispose of this equipment. Anyone carrying out the above-mentioned activities must have read this Installation &...
Warning of a dangerous situation that may possibly result in death or serious injury. CAUTION Warning of a situation that may result in minor or moderate injury. ATTENTION Warning of a situation that results in damage to property or the environment. NRS 1-56 - Installation & Operating Manual - 850142-00...
Here, we explain some abbreviations, specialist terms, etc., which are used in this Manual. NRG .. / NRS .. GESTRA equipment and type designations, see page 8. SELV Safety Extra Low Voltage NRS 1-56 - Installation & Operating Manual - 850142-00...
The NRS 1-56 level switch also indicates two alarm states, which can be configured as MIN and MAX. Overview of possible unit combinations Level switch...
Usage for the intended purpose Applicable directives and standards The NRS 1-56 level switch has been tested and approved for use in the scope governed by the following directives and standards: Directives: Directive 2014/68/EU Pressure Equipment Directive ■ ■ Directive 2014/35/EU Low Voltage Directive ■...
Check that the plant is not carrying live voltage before commencing work. ■ ■ Faulty equipment jeopardises plant safety. If the NRS 1-56 level switch does not behave as described on page 23, it may be faulty. ■ ■ Perform failure analysis.
Function The NRS 1-56 level switch measures using the conductivity principle and makes use of the electrical conductivity of the water to do this. The level switch is designed for different conductivities and for connection to four electrode rods in total.
Maximum switching current - 8 A at 250 V AC / 30 V DC - cos ϕ = 1 ■ ■ Inductive loads must have interference suppression (RC combination) as specified by the ■ ■ manufacturer Required external fuse for output contacts T2.5A ■ ■ NRS 1-56 - Installation & Operating Manual - 850142-00...
Page 13
◆ ■ 2 x 1.5 mm stranded with sleeve ◆ ■ Housing attachment: Mounting clip on support rail TH 35 (to EN 60715) ■ ■ Weight Approx. 0.2 kg ■ ■ NRS 1-56 - Installation & Operating Manual - 850142-00...
Disposal information Fig. 3 CE marking The date of production is printed on the side of the equipment. Factory settings The NRS 1-56 level switch is delivered with the following factory default settings: Function: Inlet control ■ ■ Sensitivity: > 10 μS/cm at 25 °C ■...
Front membrane with LED, see page 23 removing the lower terminal strip. Lower terminal strip Equipment settings, 4-pole code switch, for setting the function see page 22. and sensitivity Housing Support rail TH 35 NRS 1-56 - Installation & Operating Manual - 850142-00...
Installing the NRS 1-56 level switch The NRS 1-56 level switch snaps onto a TH 35 support rail in a control cabinet. DANGER There is a risk of electric shock during work on electrical systems. Switch off the voltage to the plant before you install the equipment.
Alarm 1 (MIN/MAX) electrode rod Pump 2 electrode rod Pump 1 electrode rod (pump ON for inlet control) (pump OFF for inlet control) Functional earth Tank or reference electrode Fig. 5 NRS 1-56 - Installation & Operating Manual - 850142-00...
Electrical connection Connecting the 24 V DC power supply The NRS 1-56 level switch is supplied with 24 V DC. ■ ■ A safety power supply unit that delivers a Safety Extra Low Voltage (SELV) must be used to supply the ■ ■...
When your settings are complete: Plug the lower terminal strip back in. ■ ■ Switch the mains voltage back on. The equipment restarts. ■ ■ 2 3 4 2 3 4 Fig. 12 NRS 1-56 - Installation & Operating Manual - 850142-00...
Fill the tank until the water is above the “Pump OFF” level. The Pump LED The pump relay is de-energised. The “Pump OFF” electrode rod does not light up Contacts 19/20 are open. is immersed. NRS 1-56 - Installation & Operating Manual - 850142-00...
Page 24
MIN electrode rod is no longer LED 1 or 2 lights up red, closed, 17/18 are open. immersed. depending on the configuration * Factory setting of output contacts Alarm 2 = MIN NRS 1-56 - Installation & Operating Manual - 850142-00...
LEDs flash to alert the user. If Alarm 1 and 2 are both configured as MIN or MAX alarms, there is no plausibility check of the two electrode rods. NRS 1-56 - Installation & Operating Manual - 850142-00...
Page 26
If a genuine alarm occurs, this will not be tested during the test sequence. ■ ■ Faulty equipment jeopardises plant safety. If the NRS 1-56 level switch does not behave as described in this section, it may be faulty. ■ ■ Perform failure analysis.
Disconnect all poles of the supply cable from the mains and secure so they cannot be ■ ■ switched back on. Check that the plant is not carrying live voltage before commencing work. ■ ■ NRS 1-56 - Installation & Operating Manual - 850142-00...
Check the shield connection to the central earthing point (CEP) in the control cabinet. ■ ■ Suppress HF interference using hinged-shell ferrite rings. ■ ■ Route the connecting cables to the level electrodes separately from power lines. ■ ■ NRS 1-56 - Installation & Operating Manual - 850142-00...
Check that the equipment is not live. Unscrew and pull off the upper and lower terminal strips, see Fig. 4 A; C Release the slider holder on the base of the equipment, and detach the NRS 1-56 level switch from the support rail.
EU Declaration of Conformity We hereby declare that the NRS 1-56 level switch conforms to the following European Directives: Directive 2014/35/EU Low Voltage Directive ■ ■ Directive 2014/30/EU EMC Directive ■ ■ Directive 2011/65/EU RoHS Directive ■ ■ Please see our Declaration of Conformity for details on the conformity of our equipment with European Directives.