Input Specifications (Main Unit Only) - Panasonic KW2M-A User Manual

Eco power meter
Hide thumbs Also See for KW2M-A:
Table of Contents

Advertisement

11.4 Input Specifications (main unit only)

Number of inputs
Insulation method
Input method
Input signal
Input mode
Max. counting speed
Min. input signal width
Decimal point
Pre-scale
Range
Output mode when pulse output is
selected
Protective elements
Input signal
Pulse rate
Pulse input
Input condition
Operation
voltage/current
<Internal input circuit>
KW2M-A/X User's Manual
1
Designated insulation for input (insulate to the other functions)
Contact / non-voltage contact or open-collector
・Impedance: Max. 1kΩ
(when short-circuit current: max. 10mA)
Non-voltage
・Residual voltage when shorted: max. 3V
・Impedance when open: min. 100kΩ
Pulse input or synchronized with input from external device
2000Hz / 30Hz
0.25ms (when 2000Hz is set) / 16.7ms (when 30Hz is set)
ON:OFF ratio=1:1
Under 3 digits
0.001 to 100.000 (set in setting mode)
HOLD
Zener diode
1,000 to 99,000 pulse/kWh (set in setting mode)
(External pulse converter is necessary.)
0.001 to 100.000 kWh/pulse
Pulse width
2000Hz
Pulse interval
Pulse width
30Hz
Pulse interval
5V DC 10mA
R: resistor
C: capacitor
Min. 0.25ms
Min. 0.5ms
(OFF time min. 0.25ms)
Min. 16.7ms
Min 33.4ms
(OFF time min. 16.7ms)
Specifications
85