Chapter 5 Settings - Panasonic KW2M-A User Manual

Eco power meter
Hide thumbs Also See for KW2M-A:
Table of Contents

Advertisement

Chapter 5 Settings

You can set basic parameters for measuring using the keys on the device. For setting other function
parameters, use a Web browser.
(URL: http//xxx.xxx.xxx.xxx/setup/index.htm. Set the IP address to 'xxx.xxx.xxx.xxx')
After wiring the device and the CT, turn the power on and set the parameters for power measurement,
The device can measure the electric power. In order to use the other functions, set other parameters
according to your needs.
◆Key functions in setting mode
<MODE>
<SET>
<SHIFT/∧>, <ITEM/>>
◆Parameters for power measurement
Item
Phase/Wire system
CT type
Primary side current of CT
VT secondary side voltage
VT primary side voltage
Over voltage (ON threshold)
Over voltage (OFF threshold)
Under voltage (ON threshold)
Under voltage (OFF threshold)
Over current (ON threshold)
Over current (OFF threshold)
Under current (ON threshold)
Under current (OFF threshold)
Conversion rate (P) total
Conversion rate (-P) total
Hour meter threshold
Target phase for hour meter
Cut-off current
Setup
Simple
measurement
Voltage
PF
◆Parameters for demand measurement
Item
Power demand type
Power demand interval 1
Power demand interval 2
Power input
Pulse unit
Pulse rate
(convert to electric power)
Pulse constant number
Current demand interval
KW2M-A/X User's Manual
Use this key to switch to setting mode.
Use this key to set the items and values.
Use these keys to select items and change values.
Range
1P2W, 1P3W, 3P3W 3P4W
1, 5 [A]
1 to 65535 [A]
100 to 690 [V]
100 to 500000 [V]
0.0 to 120.0 [%]
0.00 to 99.99/1kWh
01 to 100.0 [%]
Phase1, Phase2, Phase3,
All
0.1 to 50.0%
OFF, Fixed voltage/PF,
Measure one CT
0.0 to 500000.0 [V]
0.000 to 1.000
Range
Sliding block, Fixed block
1 to 60 [min.]
1 to 60 [min.]
CT (CT input),
Pulse (Pulse input)
kWh (electric power),
PLS (pulse constant)
0.001 to 100.000 [kWh]
1000 to 99000 [pulse/kWh]
1 to 60 [min.]
○: Available -: Not available
Initial value
Keys
1P2W
5A
5A
230V
230V
0.0%
10.00
10.0%
All
0.1%
OFF
230V
1.000
○: Available -: Not available
Initial value
Keys
Sliding block
15
1
CT
kWh
1.000
50000
15
Settings
Setting
Web
Setting
Web
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kw2m-xAkw263100aAkw272100a

Table of Contents