Item
10
Power factor
11
Count value
12
Over Voltage
13
Under Voltage
14
Over frequency
15
Under frequency
16
Current THD
17
Voltage THD
18
Current harmonics
19
Voltage harmonics
20
Current unbalancing
21
Voltage unbalancing
22
Power demand
23
Current demand
KW2M-A/X User's Manual
Select phase to monitor and set threshold to use for output.
*Select 'All' when measuring 3P3W.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 9999999999.99
ON threshold: 0.00 to 9999999999.99 (initial: 9999999999.99)
Set a count value to use for alarm output.
<Range>
0 to 999999 (initial: 0)
Select phase to monitor.
*The threshold is the ratio that is set at 'Setting for Power
Measurement'.
< List >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 100.00Hz (initial: 100.00)
ON threshold: 0.00 to 100.00Hz (initial: 100.00)
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 400.00% (initial: 400.00)
ON threshold: 0.00 to 400.00% (initial: 400.00)
Select phase to monitor and set threshold to use for output.
< Range >
OFF threshold: 0.00 to 300.00% (initial: 300.00)
ON threshold: 0.00 to 300.00% (initial: 300.00)
Select demand type to monitor and set threshold to use for
output.
< List & Range >
Power Type: Active, Reactive, Apparent,
Active(Export), Reactive(Export) (initial: Active)
OFF threshold: 0.000 to 999999999.999 (initial:
999999999.999)
ON threshold: 0.000 to 999999999.999 (initial: 999999999.999)
Select phase to monitor and set threshold to use for output.
< List & Range >
Target phase: Phase1, Phase2, Phase3, ALL (initial: ALL)
OFF threshold: 0.00 to 120.00% (initial: 0.00)
ON threshold: 0.00 to 120.00% (initial: 0.00)
Description
(initial: 9999999999.99)
Settings
47