How To Make Settings Using The Keys; Settings For Power Measurement - Panasonic KW2M-A User Manual

Eco power meter
Hide thumbs Also See for KW2M-A:
Table of Contents

Advertisement

5.4 How to make settings using the keys

■Set before measuring.
Select an setting item with <ITEM/>> and press <SET> and the value will be blinking. Set a new
value with the keys <ITEM/>> and <SHIFT/∧>.
When you select [Yes] in the confirmation window and press <SET>, the setting values are saved.
Setting items with (※) can be set for each CH and each unit individually.

5.4.1 Settings for power measurement

Phase/Wire system
Select phase/wire system to measure.
- 1
M
CT setting
Select the CT type used.
- 1
M
P r i m a r y
S e c o n d a r y
For CT with secondary side current 5A: [5]
For CT with secondary side current 1A: [1]
Voltage setting
Set the rated voltage to measure.
- 1
M
P r i m a r y
S e c o n d a r y
KW2M-A/X User's Manual
(※)
Press <ITEM/>>, <SHIFT/∧>.
P o
w
e r
S y s t e m
[Set list]
1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
1 P 2
W
* When the setting does not match the measured system,
the device will not measure correctly.
(※)
Press <SET> to select primary or secondary.
P o
w
e r
C T
Press <ITEM/>>, <SHIFT/∧> to select the range.
5 A
5 A
[Set range]
Primary side: 1 to 65535 (initial: 5)
Secondary side: 5 (5A), 1 (1A) (initial: 5)
SHIF
T
ITE
M >
Press <SET> to select primary or secondary.
P o
e r
w
V T
Press <ITEM/>>, <SHIFT/∧> to set the voltage.
2 3 0 V
2 3 0 V
[Set range]
Primary side: 100 to 500000 (initial: 230)
Secondary side: 100 to 690 (initial: 230)
*Set the rated voltage when no VT is used.
SHIF
T
ITE
M >
Increase
Decrease
Increase
Decrease
Settings
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kw2m-xAkw263100aAkw272100a

Table of Contents