ABB FSO-21 User Manual page 445

Safety functions module
Hide thumbs Also See for FSO-21:
Table of Contents

Advertisement

Index
Name/Value
50...59,000 ms
SAFEIO.33 DI X113:1 diag pulse
on/off
Off
On
SAFEIO.34 DI X113:2 diag pulse
on/off
Off
On
SAFEIO.35 DI X113:3 diag pulse
on/off
Off
On
SAFEIO.36 DI X113:4 diag pulse
on/off
Off
On
SAFEIO.37 DI X114:1 diag pulse
on/off
Off
On
SAFEIO.38 DI X114:2 diag pulse
on/off
Off
On
SAFEIO.39 DI X114:3 diag pulse
on/off
Off
On
SAFEIO.40 DI X114:4 diag pulse
on/off
Off
On
SAFEIO.51 DO diagnostic pulse
length
0.5 ms
1 ms
2 ms
SAFEIO.52 DO diagnostic pulse
period
50...59,000 ms
Description
Time
Sets the diagnostic pulse of digital input
X113:1 on or off.
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X113:2 on or off.
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X113:3 on or off.
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X113:4 on or off
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X114:1 on or off.
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X114:2 on or off.
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X114:3 on or off
Diagnostic pulse off
Diagnostic pulse on
Sets the diagnostic pulse of digital input
X114:4 on or off
Diagnostic pulse off
Diagnostic pulse on
Sets the length of the diagnostic pulse for
digital outputs.
Length of the diagnostic pulse is 0.5 ms.
Length of the diagnostic pulse is 1 ms.
Length of the diagnostic pulse is 2 ms.
Sets the time during which the FSO module
must receive at least one whole diagnostic
pulse.
Time
Parameters 445
Factory
default
On
On
On
On
On
On
On
On
1 ms
10,000 ms