ABB FSO-21 User Manual page 443

Safety functions module
Hide thumbs Also See for FSO-21:
Table of Contents

Advertisement

Index
Name/Value
SAFEIO.21 Safety relay 1 output Sets the digital output connected to the
None
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
SAFEIO.22 Safety relay 1
feedback
None
DI X113:1
DI X113:2
DI X113:3
DI X113:4
DI X114:1
DI X114:2
DI X114:3
DI X114:4
SAFEIO.23 Safety relay 1
feedback type
Mechanically linked
NC contacts
Mechanically linked
NO contacts
Description
safety relay 1.
To connect the safety relay to a certain
safety function, you must set the same
digital outputs in the output parameter for
that safety function. For example, if you set
parameter
SBC.21 SBC output
value as you set for the safety relay output,
the safety relay is active when the SBC
function is active.
Note: The output must always be redundant.
Otherwise the feedback signal of the safety
relay is not used (see parameter
Safety relay 1
feedback).
No output connected
Sets the digital feedback input of safety
relay 1.
Parameter
SAFEIO.23 Safety relay 1
feedback type
sets the type of the feedback
input.
No input connected
Single input X113:1
Single input X113:2
Single input X113:3
Single input X113:4
Single input X114:1
Single input X114:2
Single input X114:3
Single input X114:4
Sets the type of the feedback signal for
safety relay 1.
Note: FSO reads the feedback signal in
every state change situation, ie, when STO
is activated. The feedback delay is 800 ms
for both feedback types, that is, a feedback
signal from the safety relay must be received
within 800 ms.
Feedback of the safety relay is NC (inverted
state compared with the relay).
Feedback of the safety relay is NO (same
state compared with the relay).
Parameters 443
Factory
default
None
to the same
SAFEIO.22
None
Mechanicall
y linked NC
contacts