Advertisement

Specifications
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches 203° F ± 10° F [95°C±5°C]. An overload temperature cannot be reset until the temperature of the heatsink
is below 158° F ± 9° F [70°C±5°C] (Guideline - these temperatures may vary for different power sizes, enclosures,
etc.). The adjustable frequency drive has an auto derating function to avoid its heatsink reaching 203° F [95°C].
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
10
10
10-8
®
VLT
Refrigeration Drive Instruction Manual
®
MG16J122 - VLT
is a registered Danfoss trademark