New Door Installation - ABB Emax 2 Installation And Maintenance Manual

Direct/cic replacement of legacy ge ak 600a - 4000a circuit breakers used in akd-5 & substructures
Table of Contents

Advertisement

New Door Installation

Refer 2TSA451007P0000 for detailed installation instructions for all AKD5 Doors/Door
Adapters
Table 9
Retrofill Breaker
AKD5-AK25/Emax 1.2
AKD5-AK50/Emax 2.2
AKD5-AKT50/Emax 2.2
Below representations are provided only to show the overview of the interlock assemblies.
Danger
Install New Door
1.
Remove existing compartment door(s) and remove hinge block using #2 Phillips headed
Or Door adaptor
screw driver.
2. To install new door follow the instructions below:
2TSA451011P0000 Rev-B
Ensure only qualified personnel install, operate, service & maintain all electrical
equipment.
De-energize/switch off the LVS section that is to be retrofitted.
Open the compartment door that is to be retrofitted.
Rack out the existing legacy AKR breaker from the LVS.
Keep the door open for accessing the door mounting pads placed on the right side
wall in the LVS compartment.
Loosen the screws holding the mounting pads to the compartment frame.
Note that this will provide access for removing the old door from the LVS
compartment.
Unpack the new door assembly and mount it on the compartment and secure via
placing the hinges and tightening the screws.
Insert the new retrofitted Emax 2 Retrofill circuit breaker into the compartment and
slide the breaker into the disconnected condition.
Close the new door and secure it to the compartment.
Rack-in the new retrofitted Emax 2 Retrofill circuit breaker.
For ordering new door depending on door size and door cutouts for accommodating
lamps, ammeters & detail procedure refer to document 2TSA451007P0000
Installation Manual Number
1SXU200040C0201
1SXU200040C0201
1SXU200040C0201
It must be ensured that the supply power to
the
compartment
compartment is de-energized for all the
incoming and outgoing circuits of the LVS
prior to any work being conducted on it.
During the installation and related work on
the equipment, it must be ensured that the
operator is using the prescribed PPE for the
specified tasks.
is
turned
off/
© 2020 Emax 2 Retrofill Circuit Breakers 600A-4000A | 47