Install Cassette Rail Lever Lockout Brackets AK/AKT50 Compt's only

Figure 63
Install lock
bracket (AK-
25/AK50 +
cabinet only)
Ensure only qualified personnel install, operate, service and maintain all electrical
equipment.
1.
2.
3.
32| © 2020 Emax 2 Retrofill Circuit Breakers 600A-4000A
Check that the retrofitted Emax 2 cassette has been completely racked into the
cabinet.
Slide the bracket back into position as shown in the image below (Figure 46) and line
up the holes previously drilled with the holes on the locking bracket (figure 47).
Secure the bracket to side frame by using two self-tapping screws provided with the
kit (figure 48 & 49) .
Tools required: Spanner, 0.2-inch drill bit, hand drill.
It must be ensured that the supply power to the
compartment is turned off/ compartment is de-
energized for all the incoming and outgoing
circuits of the LVS prior to any work being
conducted on it.
During the installation and related work on the
equipment, it must be ensured that the operator
is using the prescribed PPE for the specified
tasks.
2TSA451011P0000 Rev-B