Troubleshooting Chart
Symptom
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
Furnace fails to operate
LED Status
Fault Description
Polarity of 115 volt AC is reversed
EEA
Poor unit ground
Gas valve is energized when it should not be
EEb
Internal gas valve error
Gas valve is not energized when it should be
EEC
External Gas Valve Error
Auxiliary limit switch (blower compartment) circuit
EEd
E10
Grounding Error
E11
Burner limit switch circuit is open
E12
Redundant relay open alarm
E13
Redundant relay stuck closed alarm
EbF
Inducer communication alarm
E1b
APS reference error
E1C
APS null error
E1d
APS span error
E1E
APS pressure error
E1F
APS input error
EEH
Twinning error
EbL
Low circulator current
EbU
Circulator current unexpected
EdO
No shared data
Correct polarity, check and correct wiring if necessary
Verify proper ground, correct if necessary
Check wiring in gas valve circuit
Replace integrated control board
Check wiring in gas valve circuit
Replace integrated control board
Furnace power was turned off during heat cycle.
Blower not operating during heat
is open
Faulty aux limit or wiring
Check grounding
Check and correct gas supply pressure
Check flue and air inlet for blockage, proper length,
elbows, and termination
Check wiring connection in limit circuit
Check burner temperature switch. Replace if necessary
Replace integrated control board
Replace integrated control board
Check Red, Black, White harness & connections to
inducer & control board
Check Red, Black, Green harness & connections to
pressure sensor & control board
Replace pressure sensor
Check Red, Black, Green harness & connections to
pressure sensor & control board
Check pressure hoses to pressure sensor and
pressure switch
Check Red, Black, Green harness & connections to
pressure sensor & control board
Check pressure hoses to pressure sensor and
pressure switch
Check Red, Black, Green harness & connections to
pressure sensor & control board
Replace pressure sensor
Check Red, Black, Green harness & connections to
pressure sensor & control board
Replace pressure sensor
Check motor 120V line wire is connected to terminal
inside current transformer loop
Check wire connections to motor and PCB
Check motor 120V line wire is connected to terminal
inside current transformer loop
Populate shared data set using memory card
29
Corrective Actions