FIRE CONDITIONS

In the event of a fire condition:
• the panel's general Fire indicator will flash;
• the panel's internal sounder (if enabled) will pulse;
• the relevant Fire Zone indicator on the panel will flash;
• the panel's display will show the number and name of the zone in fire (see example below); and
• the system's sounders, relays and other output devices will operate as programmed.
Number of zone in fire
Last zone:
Pressing the More Information button will display the actual device that has triggered the fire
condition, for example:
Number of activated
devices within the zone
1 of 1 Alarms in: Zone 1
North stairs : Detector near exit
Name of zone in fire
In the event of a fire condition on multiple zones:
• the panel's general Fire indicator will flash, its internal sounder (if enabled) will pulse and its
relevant Fire Zone indicators will flash;
• the panel's display will show the first and last zones that went into fire together with the total
number of zones that are in fire. For example, if a fire condition has occurred in zones 1, 2 and 3
in that order, the display will show a message similar to the one below.
• the system's sounders, relays and other output devices will operate as programmed.
1st Zone: 1: North Stairs
Lastzone: 3: Ground Floor
To view any additional zones that are in fire, press the
continue to show the last zone that went into fire but all previous zones will now appear on a step-
by-step basis with details of which order they went into fire, i.e. 1st zone, 2nd zone, etc.
Pressing the More Information button at any time will give you details of the actual device(s) that are
in a fire condition on the zone that is on the top line of the display. These can be scrolled through
5
6
using the
and
buttons.
In the event of a fire condition, the building's fire management plan should always be
executed.
Authorised users can silence or reset the system as appropriate by entering access level 2 and pressing
the buttons on the panel's front. Details on how to do this can be found on page 14.
FIRE CONDITIONS WITH OUTPUT DELAYS
If a fire condition occurs on a zone that has been programmed with one or more output delays, the
panel will report the fire condition as described above but the panel's Delays Running indicator will
flash yellow to indicate that one or more of the zone's assigned outputs has not yet triggered. Details
of which outputs have delays running can be viewed by pressing the More Information button.
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 9 of 28
www.acornfiresecurity.com
Name of zone in fire
System status
1:North Stairs
1 Zones
Total number of
zones in fire
Number of zone in fire
Device description
www.acornfiresecurity.com
:FIRE!
If more than one device is in a fire
condition on the zone, the top left
corner of the display will show, for
example "1 of 3" and can be scrolled
through using the
:FIRE!
3 Zones
5
6
or
buttons as appropriate. The display will
5
6
and
buttons.