XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

Disabling or enabling parts of the system

Selecting this menu option takes you to the disablements sub-menu which allows you to enable or
disable zones, sounders, outputs, relays, individual devices and/or the panel's fault relay.
We strongly recommend all disablements are regularly reviewed and immediately enabled when no
longer necessary as they can have a major effect on how the system works.
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, pre-alarms, etc., and is normally
used to temporarily disable a zone of detectors/call points in areas such as loading bays where they are
prone to nuisance triggering from vehicle fumes. When selected, press the Accept
window similar to the one below will appear:
Zone: 1: Shop Floor
Enabled
Select the zone to be disabled/enabled using the
zone's status (Enabled or Disabled) will flash. Next, use the
enabled and disabled and press the Accept
The window will now move to the next available zone allowing further enablements or disablements
to be made. Alternatively, to return to the previous menu press the Escape
Please note: if all the input devices on a zone have been individually disabled using the ENABLE/DISABLE
DEVICES function described on page 18, the zone they belong to will also be disabled. If you try to re-
enable a zone which has no enabled devices on it, a prompt appears saying this cannot be done.
Instead you must first enable at least one device on the zone using the ENABLE/DISABLE DEVICES
function before re-enabling the zone itself.
ENABLE/DISABLE SOUNDERS
This function allows you to disable one or more sounder groups from sounding in a fire condition.
When selected, press the Accept
Sounder Group: 1
Select the sounder group (1 to 16 or ALL) to be disabled/enabled using the
When the desired sounder group has been selected, press the Accept
group's status (Enabled or Disabled) will flash. Next, use the
enabled and disabled and press the Accept
move to the next sounder group allowing further enablements or disablements to be made.
Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from sounding in a fire condition. It is typically
used to disable, for example, auto-diallers and other ancillary equipment from activating during routine
maintenance. When selected, press the Accept
Output Set: 1
Select the output set (1 to 16 or ALL) to be disabled/enabled using the
When the desired output set has been selected, press the Accept
status (Enabled or Disabled) will flash. Next, use the
disabled and press the Accept
next output set allowing further enablements or disablements to be made. Alternatively, to return to
the previous menu press the Escape
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 17 of 28
www.acornfiresecurity.com
5
and
4
button to select the desired option.
4
button and a window similar to the one below will appear:
4
button to select the desired option. The window will now
4
button and a window similar to the one below will appear:
5
4
button to select the desired option. The window will now move to the
3
button.
www.acornfiresecurity.com
6
buttons. Press the Accept
5
6
and
buttons to toggle between
3
button.
5
and
4
button once and the sounder
5
6
and
buttons to toggle between
3
button.
5
6
and
4
button once and the output set's
6
and
buttons to toggle between enabled and
4
button and a
4
button and the
6
buttons.
buttons.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp502/hXfp501/xXfp501/hXfp

Table of Contents