C-TEC XFP502/X User Manual page 18

Networkable analogue addressable fire alarm control panel
Hide thumbs Also See for XFP502/X:
Table of Contents

Advertisement

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel's 3 auxiliary relays from activating as
programmed. When selected, press the Accept
Panel Relay:- 1
Select the relay (1, 2 or 3) to be disabled/enabled using the
When the desired relay has been selected, press the Accept
Disabled) will flash. Next, use the
4
the Accept
button to select the desired option. The window will now move to the next relay
allowing further enablements or disablements to be made. Alternatively, to return to the previous
3
menu press the Escape
ENABLE/DISABLE DEVICES
This function allows loop devices to be disabled from reporting faults, fires, pre-alarms, etc., and is
normally used to temporarily disable detectors/call points that are nuisance tripping. When selected,
4
press the Accept
button and a window similar to the one below will appear:
Select Zones:- 1: Shop Floor
5
6
Use the
and
buttons to select the zone where the device you wish to disable/enable is located.
When selected, press the Accept
that zone will appear, e.g.
Shop Floor:- 1: Gent WC
Loop 1, Device 3: Enabled
5
6
Use the
and
buttons to scroll through the available devices. When the desired device appears,
4
press the Accept
button and the device's status (Enabled or Disabled) will flash. Next, use the
5
6
and
buttons to toggle between enabled and disabled and press the Accept
desired option. The window will now move to the next device allowing further enablements or
disablements to be made. Alternatively, to return to the previous menu press the Escape
Please note: if all the input devices on a zone are individually disabled, the zone they belong to will also
be disabled. If you try to re-enable a zone which has no enabled devices on it using the ENABLE/DISABLE
ZONES function described on page 17, a prompt appears saying this cannot be done. Instead you must
first enable at least one device on the zone before re-enabling the zone itself.
ENABLE/DISABLE FAULT RELAY
This function can be used to suppress the panel's fault relay from activating in a fault condition. When
selected, press the Accept
Fault relay is:- Enabled
5
6
Use the
and
buttons to toggle between enabled and disabled and press the Accept
select the desired option. Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE OUTPUT DELAYS
This function can be used to globally disable or enable any delays to outputs that have been programmed
into the panel. When selected, press the Accept
Delays to Outputs are:-
Enabled
5
6
Use the
and
buttons to toggle between enabled and disabled and press the Accept
select the desired option. Alternatively, to return to the previous menu press the Escape
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 18 of 28
www.acornfiresecurity.com
4
button and a window similar to the one below will appear:
5
6
and
buttons to toggle between enabled and disabled and press
button.
4
button and a list of all devices that can be disabled or enabled in
4
button and the following window will appear:
4
button and the following window will appear:
www.acornfiresecurity.com
5
6
and
buttons.
4
button and the relay's status (Enabled or
4
button to select the
3
button.
4
button to
3
button.
4
button to
3
button.