Replacement Of Parts; Returning Parts For Repair - Endress+Hauser nivocompact FTC 831 Installation And Operating Manual

Level limit switch
Table of Contents

Advertisement

Replacement of Parts

Replacement of Parts
Replacing the Electronic Insert
Switch off all sources of power to the Nivocompact.
• Remove the electrical connections to the electronic insert.
• Loosen the central screw in the electronic insert.
• Lift out the electronic insert from the housing using the handle.
• Push the new electronic insert carefully into the plug in the housing.
• Tighten the central screw.
• Connect up the electrical wires.
• Switch on the power supply.
• Carry out a new capacitance calibration with an empty silo.
• Set the switching delay.
• Select the same fail-safe mode as it was for the previous electronic insert.
• Check operation.
Replacing the Probe
• Remove, install and connect in the same way as for shortening the cable,
see Page 26.
• Carry out a new capacitance calibration with an empty silo.
• Check operation.

Returning Parts for Repair

If a Nivocompact FTC 831 cannot be repaired and needs to be sent back to
Endress+Hauser, then please note the following:
Remove all material residue attached to the probe.
This is especially important as the material may be of a dangerous nature
e.g. corrosive, poisonous, carcinogenic, radioactive etc.
Please return parts only after they have been thoroughly cleaned of
dangerous materials. Check in particular scratches and the possibility of
diffusion through plastic material.
When returning the probe, please state exactly the material in which it was
used and its characteristics.
A brief description of the error will also help us to diagnose the reason for it
and at the same time lower your costs.
Thank you for your cooperation.
Removal
Insertion
Calibration
Cleaning the Probe
Stating Material and Defect