Calculating The Battery Size; 1: Nfpa Battery Requirements; 2: Selecting And Locating Batteries - Fire-Lite Alarms MS-9200UD Manual

Fire alarm control panel
Table of Contents

Advertisement

Calculating the Battery Size

7.4 Calculating the Battery Size
Table 7.4 Total Secondary Power Requirements at 24 VDC
Secondary Standby Load
(total from Table 7.3 Calculation
Column 3)
[
]
Primary Alarm Load
(total from Table 7.3 Calculation
Column 2)
[
]
Sum of Standby and Alarm Ampere Hours
Multiply by the Derating Factor
Battery Size, Total Ampere Hours Required
MS-9200UD PN 51906:A 12/10/02
Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH).
This total load determines the battery size (in AH), required to support the control panel
under the loss of AC power. Complete Table 7.4 as follows:
1. Enter the totals from Table 7.3 on page 166, Calculation Columns 2 and 3 where
shown
2. Enter the NFPA Standby and Alarm times (refer to 'NFPA Requirements' below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and
Alarm ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size
(in AH)
5. Write the ampere hour requirements on the Protected Premises label located
inside the cabinet door
Required Standby Time
(24 or 60 hours)
X[
]
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
X[
]
7.4.1 NFPA Battery Requirements
NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby
power followed by 5 minutes in alarm
NFPA 72 Central, Auxiliary and Remote Station Fire Alarm Systems require 60
hours of standby followed by 5 minutes in alarm. Batteries installed in a system
powered by a generator need to provide at least 4 hours of standby power
7.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 7.4 . The
control panel can charge batteries in the 7 AH to 18 AH range. The control panel
cabinet is capable of housing batteries up to 18 AH. Batteries larger than 18 AH require
a UL listed external battery charger and cabinet such as the BB-26, BB-55F or other UL
listed external battery cabinet.
Power Supply Calculations
=
AH
=
AH
=
AH
X 1.2
=
AH
167

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200ude

Table of Contents