System Sensor EM-1SRI Installation And Maintenance Instructions
System Sensor EM-1SRI Installation And Maintenance Instructions

System Sensor EM-1SRI Installation And Maintenance Instructions

Supervised control module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
www.DataSheet4U.com
EM-1SRI Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Standby Current:
Alarm Current:
Maximum NAC Circuit Line Loss:
Power Supply Monitor
Maximum (Speakers):
Maximum (NAC):
Trouble Range:
Max NAC Current Rating:
Temperature Range:
Humidity:
Dimensions:
Accessories:
BEFORE INSTALLING
This information is included as a quick reference installa-
tion guide. Refer to the appropriate control panel installa-
tion manual for detailed system information. If the modules
will be installed in an existing operational system, inform
the operator and local authority that the system will be
temporarily out of service.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
Control Module, Model EM-1SRI, is used to switch an ex-
ternal power supply or audio amplifier to notification ap-
pliances. In addition to switching the external power, the
device will monitor the wiring (while external power is
not switched to the auxiliary devices) to the auxiliary de-
vice for open and short circuits via an end of line resistor.
This module is capable of Class A or Class B operation.
The module also has on-board short circuit isolators to pre-
vent shorts on the signaling line circuit from disabling more
than one device on the intelligent loop.
The control module will also have the capability to moni-
tor the external power input for loss of power (DC volt-
age supplies only). This feature can be disabled through
device configuration programming. If the external power
is switched to the auxiliary devices and there is a loss of
the DC supply, the control module has the capability of
running an algorithm in which the device will switch back
to monitor mode and check the line for short circuits. If
D500-54-00
15 to 30 VDC
630 µA max. average (continuous broadcasts)
2 mA (red LED on)
4 VDC
70.7 V RMS. 50 W
Regulated 24VDC
0 to 2 VDC
For Class B wiring system, 3A
For Class A wiring system, 2A
32°F to 120°F (0°C to 49°C)
10 to 93% RH Noncondensing
4.17˝ H x 4.26˝ W x 1.22˝ D; (106 mm H x 108 mm W x 31 mm D)
39 kΩ End of Line Resistor Part # A2263-00 (included)
Wall cover plate (included)
SMB500 Surface Mount Electrical Box
A2143-60 Bypass capacitor
EA-CB Control Module Barrier
no short exists, the device will reapply the external power.
This algorithm can be enabled when using a DC external
supply that is guaranteed to be above 9 volts.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected
to a listed compatible control panel.
MOUNTING
The module mounts directly to 4˝ square electrical boxes.
The box must have a minimum depth of 2
must be mounted with the arrow facing upward for proper
operation of the IR configuration tool (model no. EA-CT).
Surface mounted electrical boxes (SMB500) are available
from System Sensor.
WIRING
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job draw-
3. Set the address on the module per job drawings using
4. Secure module to electrical box (supplied by installer).
1
3825 Ohio Avenue, St. Charles, Illinois 60174
ings and appropriate wiring diagrams. Optional EA-CB
may be required to separate power limited and non
power limited wiring in the electrical box (see Figure
1B). 2.
For new installations use the enclosed 39
kΩ EOL resistor. For retrofit applications where the ex-
isting 47 kΩ cannot be easily replaced, it may be left in
place without loss of performance.
the IR configuration tool (model no. EA-CT).
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
1
/
˝. Modules
8
I56-2016-004

Advertisement

loading
Need help?

Need help?

Do you have a question about the EM-1SRI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor EM-1SRI

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS www.DataSheet4U.com 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 EM-1SRI Supervised Control Module www.systemsensor.com SPECIFICATIONS Normal Operating Voltage: 15 to 30 VDC Standby Current: 630 µA max. average (continuous broadcasts) Alarm Current: 2 mA (red LED on) Maximum NAC Circuit Line Loss: 4 VDC Power Supply Monitor Maximum (Speakers): 70.7 V RMS. 50 W Maximum (NAC): Regulated 24VDC Trouble Range: 0 to 2 VDC Max NAC Current Rating: For Class B wiring system, 3A For Class A wiring system, 2A Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% RH Noncondensing Dimensions: 4.17˝ H x 4.26˝ W x 1.22˝ D; (106 mm H x 108 mm W x 31 mm D) Accessories: 39 kΩ End of Line Resistor Part # A2263-00 (included)
  • Page 2 Auto Addressing TESTING Eclipse Series devices are capable of supporting auto ad- The following resistance values can be used to test the www.DataSheet4U.com dressing, if the fire alarm control panel is designed to do module after installation: so. In auto addressing, the control panel, through the use Short Circuit: <50Ω of each device’s on-board isolators, can automatically as- Open Circuit: >1MΩ...
  • Page 3 Figure 2: Typical Class B, Style Y NAC configuration. SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. www.DataSheet4U.com TWISTED PAIR RECOMMENDED ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED FROM PANEL OR PREVIOUS DEVICE MODULE POLARITIES ARE – (–) SHOWN IN ALARM (–) (–) –...
  • Page 4 Figure 5: Typical Class A, Style Z Audio NAC configuration. www.DataSheet4U.com ALL WIRING SHOWN IS SUPERVISED SIGNAL LINE CIRCUIT (SLC) 30 VDC MAX. TWISTED PAIR RECOMMENDED FROM PANEL OR SPEAKERS MUST BE LISTED FOR FIRE PROTECTION PREVIOUS DEVICE – (–) –...