Safety instructions

3

Residential applications

3 Safety instructions
3.1 Residential applications

3.2 Notes about usage

Note:

3.3 Notes on communication

Cable requirements
Note:
12 | 30
The Climatix touch panel is designed for applications in most residential
environments. The technical design specification ensures that the product works
stably at temperatures of -10 °C...+50 °C (+14 °F − +122 °F).
Maximum Ambient Temperature is 50 °C (122 °F).
The Climatix touch panel is designed for indoor and outdoor use. Before putting the
Climatix touch panel into operation, ensure that it is installed correctly and the
working environment meets the conditions specified in Technical specifications
[➙ 25].
Contact your supplier first, if you have to use the Climatix touch panel in
environment where the condition requirement cannot be met.
Do not use in conditions at risk of damage, such as combustible gas, steam or
dust.
Do not use in environment with sharp temperature change or in high humidity.
Otherwise the touch panel may be damaged due to internal condensation.
The Climatix touch screen is made of glasses. Do not knock at it heavily or with
pointed or sharp objects. Otherwise you may damage the glasses and injure
yourself.
The touch panel supports the following connections to an external control device:
RS485 connection by using a dedicated communication cable
(POL0C1.75/STD or POL0C1.80/STD).
IP connection over Ethernet by using a dedicated communication cable
(POL0C1.80/STD).
The maximum length of an RS485 cable is 3 m.
If there is a communication problem, the LCD displays an error message "No
Device Response" and clears the message when communication is normal.
Do not route the communication cable together with an AC or DC power cable, nor
near a source of electrical noise. Make sure that both ends of the cable are
connected tightly and firmly.
The RS485 port is a communication port. It cannot be used for programming.