DLS FlexxPump 125 Quick Start
Hide thumbs Also See for FlexxPump 125:

Advertisement

Quick Links

The FlexxPump 125 DLS only processes the control signals listed
in the table up to a maximum length of 14 seconds. If a high level
(+24 V DC) exceeds the defined tolerance level, the FlexxPump 125
DLS does not react. If a high level (+24 V DC) is applied to PIN 2
of the electrical interface for longer than 15 seconds the LCD will
display --- and the FlexxPump 125 DLS does not react.
Control signal 2 seconds
Immediately after the control signal drops the motor run of the
FlexxPump 125 DLS starts and 0.16 cm³ lubricant is conveyed to the
outlet. Simultaneously, the FlexxPump 125 DLS sends a low level
output signal to the external controller (PLC) to confirm the duration
of the motor run.
In order to ensure a reliable and unambiguous recognition of
the control signal a break must be observed. The control signal 2
seconds requires a break time of at least 22 seconds between two
identical or different control signals.
Control signal 12 seconds
The control signal 12 seconds triggers the FIL function by the
external control.
Control signal 14 seconds
The control signal 14 seconds is used to acknowledge error
messages of errors E2 and E3.
LCD
Description
Output signal (PIN 4)
OFF
switched off
low, permanent
PUL
ready for operation
high, permanent
PUL
received control
high, permanent
blinking
signal
----
Received control signal longer than 15 seconds
01..50
dispensing process
low, 10...18 seconds
E1
cartridge empty
0,5Hz square wave signal, permanent
E1
cartridge error
low, permanent
E2
overload
low, permanent
E3
undervoltage
low, permanent
E4
fatal error
low, permanent
Additional character on the LCD
Displayed when the cartridge is empty and needs to be
replaced.
MAX
After each cycle the maximum back pressure is displayed
in bar.
The FlexxPump 125 DLS does not process any control signals until
all errors have been eliminated.
Error E2 (overload) must be acknowledged with the control signal
14 seconds after elimination of the cause(s).
Error E3 (undervoltage) must be acknowledged with the control
signal 14 seconds after elimination of the cause(s).
6. Maintenance
NOTICE
A used lubricant cartridge must not be replaced on the FlexxPump
125 DLS as the integrated stroke counter of the FlexxPump 125
DLS is automatically reset by the cartridge sensor after a cartridge
has been removed. Only use full lubricant cartridges.
Rev.: SG-20210914
QuickStart
FlexxPump 125 DLS

Advertisement

loading

Summary of Contents for DLS FlexxPump 125

  • Page 1 NOTICE (+24 V DC) exceeds the defined tolerance level, the FlexxPump 125 DLS does not react. If a high level (+24 V DC) is applied to PIN 2 A used lubricant cartridge must not be replaced on the FlexxPump of the electrical interface for longer than 15 seconds the LCD will 125 DLS as the integrated stroke counter of the FlexxPump 125 display --- and the FlexxPump 125 DLS does not react.
  • Page 2 The FlexxPump 125 DLS provides the following unalterably defined 4. Commissioning control signals (input signals) which must be transmitted from the Housing PLC to the FlexxPump 125 DLS via PIN 2 of the electrical M12x1 Mechanical fastening Mounting options backside: female thread M5 (2x) interface as high level (+24 V DC).