Install the level meter in the vertical  position into the upper lid of the tank or reservoir using a weld-
ing flange, a fastening nut or a flange so that the
level meter axis is perpendicular to the surface level
of the measured liquid (Fig. 1).
    T he min. dimensional  parameters to install the level
meter into a lid or a ceiling of a tank are given in Fig. 3.
When installing in an open channel (reservoir, drain
etc.), install the level meter onto a bracket as close as
possible to the expected max. level.
In connection with the measurement principle, no sig-
nals reflected in the area immediately under the level
meter can be evaluated. The  zone (Fig. 2) determines
the min. distance possible between the level meter
and the highest surface level. The min. distances to
the medium are given in the chapter "Specifications".
It is necessary to install the level meter so that the
bin level cannot interfere with the dead zone when
filled up to the maximum. If the measured level inter-
feres with the dead zone, the level meter will not work
properly.
Fig. 2: Level meter dead zone
If the maximum surface level in the tank interferes with the dead zone, the level meter has
to be mounted into a higher installation  neck. In this way, the tank can be fi led nearly up to
the maximum volume. The inner neck surface has to be even and smooth (without edges and
welded joints); the inner edge should be rounded where the ultrasonic wave leaves the pipe. The
neck diameter should be as large as possible but the neck height should be as low as possible.
Recommended dimensions of the input neck are given in Fig. 4.
a – Neck height
b – Neck width
m – Dead zone (blind zone, blocking dist.)
Fig. 4: Possible installation of the installation neck
5
Fig. 1: Recommended installation in
UPS 1000–06
UPS 1000–20
m – Dead zone
(blind zone, blocking distance)
Fig. 3: Installation distance from the tank wall
the tank
UPS 1000–02 ; 10 d > 1/12 c
(min. 200 mm)
d > 1/8 c
(min. 200 mm)
d > 1/10 c
(min. 200 mm)
d – Distance from
the tank wall
c – Maximum reach
of the level meter
a < 3 b
UPS 1000–02 ; 06
b > 100 mm
a < 1,5 b
UPS 1000–10
b > 100 mm
a < 1,5 b
UPS 1000–20
b > 150 mm
Ultrapro-1000