Operational Sequence & Troubleshooting Flow Chart - Calorex Aquatherm DIGITAL LOGIC AT1000 Owner Operational Manual

Swimming pool & spa heat pumps black cabinet with digital controls only
Table of Contents

Advertisement

Operational Sequence & Troubleshooting Flow Chart
for "Digital Logic" Digital Control Models
220V Power
To Heater
Green Power Light
On
Heater
Stays Off
Possible Bad
T-Stat Board, Pot
or Sensor
Heater Shuts Off
HP Displayed
Too Much Refrig.
or Low Water Flow
or Bad Hi Switch
Try Again or
Possible Bad
Time Delay
or Below 45 to 50
Deg. Air Temp
TIME DELAYS
30 second compressor delay when switching pool/spa modes.
5 minute compressor delay when T.C.O. enables in pool mode.
5 minute T.C.O. off delay when: switching from spa to pool mode, when temperature is
reached in pool mode, or if LF (low water flow) is displayed on LED.
If water pump loses prime there will be a 3 minute compressor delay.
Water Pump
Timer Activates
Water Temperature
is Above Setting
T-Stat Relay
Does Not Close
High Pressure
Switch Open
Heater Does
Not Activate
After Delay Period
Water Pump
Starts Flowing
Water Pressure
SW Closes
Thermostat
Sensor
Water Temperature
is Below Setting
T-Stat Relay
Closes
Fan Starts
To Run, Green
Heating Light On
Low Pressure
Switch
Low Pressure
SW Closed
All OK
High Pressure
Switch
High Pressure
SW Closed
All OK
Compressor Runs
or 3 to 5 Min.
Delay Activates
Compressor Starts
Green Heating
Light ON
Page 11
Water Press. SW
Stays Open
Low Pressure
Switch Opens
LF displayed on LED
Water Rises To
Set Temp.
LF Readout
Displayed on LED
No Water Flow
To Heater or
Bad Water SW
Compressor Stops
Fan Runs
1 Hour Time Delay
Activates
Time Delay Passes or
Air Temp. Increases
Safety Control Resets
Compressor
Restarts
or Below 45 to 50˚F
Air Temp or
Bad Low Press. Sw.
Heater & Green
Heating
Light Go Off