5-3. Special Function Instruction

Conditions of anti-freezingprohibition of frequency rising:
Condition 1: in the case of anti-freezingfrequency decreasing, the temperature of indoor heat exchanger rises to
"anti-freezing frequency decreasing temperature".
Condition 2: in normal operation, the temperature of indoor heat exchanger reaches "anti-freezing prohibition of
frequency rising temperature".
Either of the above two conditions is met, the product will enter anti-freezing prohibition of frequency rising state.
Anti-freezing prohibition of frequency rising operation: the compressor is kept at the current frequency, which may
decrease according to situations while cannot rise. The outdoor fan runs.
Condition for the end of anti-freezing prohibition of frequency rising state: when the temperature of indoor heat
exchanger rises to "anti-freezing releasing temperature", the state of anti-freezing prohibition of frequency risingis
released.
Conditions for defrosting:
A:When the heating compressor consecutively runs for 40 minutes (EEPROM setting value at the current
operating mode);
B:If the ambient temperature minusthe temperature of coiled pipe is equal to or higher than six degrees
centigrade (EEPROM setting value in the current operating mode);
C:If the temperature of coiled pipe is equal to or lower than minus two degrees centigrade (EEPROM setting
value in the current operating mode);
If the above three conditions are met simultaneously, defrosting begins.
Defrosting actions:
The compressor stops, and the outdoor fan stops after delay of 30 seconds; in 50 seconds the four-way
valve is power off; and in 10 seconds the compressor starts and runs at "defrosting frequency".
Conditions for ending defrosting:
Defrosting is over if either of the below conditions is met.
A:The accumulated time of defrosting is longer than 12 minutes (EEPROM setting value in the current
operating mode);
B:If the temperature of coiled pipe is equal to or higher than 14 degrees centigrade (EEPROM setting value
in the current operating mode);
Actions of exiting the defrosting state:
The compressor stops, and 50 seconds later the four-way valve opens, and another 10 seconds later the
compressor and outdoor fan restart and begin normal operation.