Hisense AS-09TR4RMEDJ00 Service Manual page 7

Table of Contents

Advertisement

Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification.
At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt
consult the manufacturer's technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
– The charge size is in accordance with the room size within which the refrigerant containing parts
are installed;
– The ventilation machinery and outlets are operating adequately and are not obstructed;
– If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant;
– Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
– Refrigeration pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless the
components are constructed of materials which are inherently resistant to being corroded or are
suitably protected against being so corroded.
6-9
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures.
If a fault exists that could compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue operation, an
adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised. Initial safety
checks shall include:
– That capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
– That there no live electrical components and wiring are exposed while charging, recovering or
purging the system;
– That there is continuity of earth bonding.
7.
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of connections, terminals not made to
original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the
purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer'sspecifications.
NOTE:
The use of silicon sealant may inhibit the effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to be isolated prior to working on them.
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents