Carbon Monoxide Gas Test

The following steps must be performed when conducting a calibration or calibration verification test (bump test) to ensure proper
performance of the monitor. Failure to do so may adversely affect product performance and result in sickness or death.
 When performing a calibration or calibration verification test (bump test) only use certified calibration gas at the required
concentration level. Do not calibrate with expired calibration gas.
 If the instrument cannot be calibrated, do not use until the reason can be determined and corrected.
 Do not cover or obstruct display or visual alarm cover.
 Ensure sensor inlets are unobstructed and is free of debris
General
A Field Calibration Kit, CM6-FCK, is needed to complete a CO gas test. These are available through local distribution or from Macurco.
Contents of the FCK
CM6-FCK: (2) Gas Cylinders, (1) 17L 50ppm carbon monoxide (CO) in air and (1) 17L 200 ppm carbon monoxide (CO) in air
Gas regulator with about two feet of plastic tubing
Humidifier
CM-6-CH calibration hood
FCK Information
Several detectors can be calibrated with one FCK. The only limitation is the amount of gas in the cylinder. The 17 liter cylinder has
approximately 85 minutes of continuous calibration run time. Replacement cylinders are available. The gas cylinder should be replaced
when the pressure gauge on the regulator shows 25-psi or less.
Note: For optimum test results it is suggested that the unit be in clean air, green light on, and be in a low ambient air flow
Gas Testing
Testing the Fan Relay
1.
Remove the Philips screw on the front of the CM-6. Remove the front cover.
2.
Open the FCK. Connect the 50 ppm gas cylinder to the regulator.
3.
Check the pressure gauge on the regulator. If you have 25-psi or less you will need to replace the gas canister.
4.
Assemble regulator, hose and Test Hood and place the Test Hood over the CO sensor.
Note: The time to activate the Fan relay depends on the delay setting.
! WARNING