Endress+Hauser Prosonic M FMU40 Brief Operating Instructions page 31

Ultrasonic level measurement
Hide thumbs Also See for Prosonic M FMU40:
Table of Contents

Advertisement

Prosonic M FOUNDATION Fieldbus
5.7.4 Function "start mapping" (053)
ENDRESS + HAUSER
+
E
This function is used to start the interference echo mapping up to the distance given in "range
of mapping" (052).
Selection:
• off:no mapping is carried out
• on: mapping is started
5.7.5 Function "dist./meas.value" (008)
ENDRESS + HAUSER
+
E
The distance measured from the reference point to the product surface and the level calculated
with the aid of the empty alignment are displayed again. Check whether the values correspond
to the actual level or the actual distance. The following cases can occur:
• Distance correct – level correct -> basic setup completed
• Distance incorrect – level incorrect -> a further interference echo mapping must be carried
out "checkdistance"(051).
• Distance correct – level incorrect -> check "emptycalibr."(005).
5.7.6 Return to group selection
After the basic setup, an evaluation of the measurement with the aid of the envelope curve
("display" (09) function group) is recommended.
ENDRESS + HAUSER
+
E
Endress+Hauser
Commissioning
After 3 s, the following
message appears
31

Advertisement

Table of Contents
loading

Table of Contents