Mount
1. Push the unit in and down to catch the rail
hook on top of the rail.
2. Rotate the bottom of the unit in toward the
rail.
3. The rail clasp will audibly "snap" into place.
If the DIN-A-MITE does not snap into place,
check to see if the rail is bent.
4. Mount the cooling fins vertically.
ç
3
WARNING:
Only authorized and
qualified personnel should
be allowed to install and
perform preventive and
corrective maintenance on
this unit. Failure to follow
this guideline could result
in damage to equipment,
and personal injury or
death.
5
WARNING:
Hot surface, do not touch
the heat sink. Failure to
follow this guideline could
result in personal injury.
ç
Mount the cooling fins
vertically.
4
Find Quality Products Online at:
1
2
Unit Dimensions - Rail-Mounted
Top
Side by side
clearance
for wire routing
13 mm
(0.50 in)
83 mm
(3.25 in)
GlobalTestSupply
www.
Dismount
4
3
1
1. Press down on the release tab while rotating
the unit up and away from the rail.
Front
124 mm
(4.88 in)
DIN-EN 50022 35 mm by 7.5 mm rail
(clipping distance 34.7 mm (1.366 in)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Side
94 mm
(3.69 in) 75 mm
(2.97 in)
Rail release tab
(pull down)
102 mm (4.00 in) clearance for air flow
and wire bending radius
Zero electrical clearance required
WATLOW DIN-A-MITE Style B User's Manual
Allowance for #8 fastener,
54 mm
metric = M4
(2.11 in)
46 mm
(1.81 in)
Grounding screw (#6)
38 mm
(1.51 in)
83 mm
(3.25 in)
49 mm
(1.92 in)
Allowance for #8 fastener,
49 mm
(1.91 in)
metric = M4
to 35.3 (1.390 in)
26 mm
(1.03 in)
102 mm
(4.00 in)
40 mm
(1.56 in)
71 mm
(2.80 in)
102 mm
41 mm
(4.00 in)
(1.60 in)
.com