Samsung AP80S0A Series User & Installation Manual page 40

Table of Contents

Advertisement

Selecting the insulator of the refrigerant pipe
f Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.
X
f The standard condition for indoor temperature is 30°C with humidity less than 85%. If the condition is out of this standard
X
condition, use the pipe that is one grade thicker.
Pipe diameter (mm)
ø 6.35~ø 19.05
ø 22.23~ø 31.75
ø 38.10~ø 44.45
-
Insulating refrigerant pipe
f Pipe insulation
X
- Insulation of the gas and liquid pipes can be in contact with each other but they should not be pressing each other.
- When contacting the gas side and liquid side pipe, use thicker insulation.
Insulation
Gas pipe
• Make sure to install the insulation so that there is no gap or crack and use the adhesives on the connection part of it
to prevent moisture from entering.
CAUTION
• Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When winding the insulation
tape, make sure that the thickness of the insulator does not get any thinner.)
• Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.
• If the thickness of the insulation gets thinner, use additional insulation.
Additional
insulation
PAC_아프리카 중동향AP80S0A_IBIM_34514A-02_EN.indd 39
Minimum thickness of the insulator
PE material
EPDM material
13
19
25
32
Insulation
Liquid pipe
Hanger
a
Insulation for
a x 3
refrigerant pipe
10
If the installation place has high humidity (such as
13
basement of a building, seaside, near hot spring
or lake etc.) increase the minimum thickness to
19
next size up for each pipes.
25
Remarks
39
2015-04-23 오후 2:18:59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ap0as0a series

Table of Contents