Dn Setting - Toshiba RBC-AMSU51 -ES Installation Manual

Wired remote controller
Table of Contents

Advertisement

7. DN setting

Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting the
setting operation.)
DN setting
Indoor unit
Code (DN) I.DN
Outdoor unit
Code (DN) O.DN
Return
DN setting
Code
(DN) I.DN
Data
0010
0000
Return
Fix
<
DN setting
Code
(DN) I.DN
Data
0010
0001
Return
Fix
<
DN setting
Continue?
Return
Yes
NOTE
• The following changes are settings to be configured by installation and service personnel.
If they are set incorrectly, trouble such as the product becoming inoperable may occur.
• For indoor units which do not support the functions below, the following DN code settings may not be possible.
• Do not perform header/follower connection for a remote controller which does not support the functions below.
• For operation when connected to an air conditioning control system which does not support the functions below, refer
to "Changing the temperature" in the Owner's Manual.
DN
77
Dual set point setting
Set
>
>
No
Item
0000: Normal automatic
0002: Dual automatic
1
Push the [
"7. DN setting" on the "Field setting menu"
screen, then push the "
F2] button.
Push the [
the indoor unit or outdoor unit and push the
"
Set
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
Move the cursor to select "Code(DN)" with the
"
<
"Code(DN)" with the [
button.
Move the cursor to select "Data" with the
"
>
with the [
2
Refer to the Installation Manual supplied
with the indoor unit or service manual for
details about the Code(DN) and Data.
3
Push the [
Code(DN) and Data. After "Continue?" is
displayed on the screen, push the
"
Yes
4
Push the "
finish the setting operation. " Setting"
appears on the screen for a while, then the
screen returns to the "Field setting menu"
screen.
Pushing the "
displays the unit selection screen when the
group control is used. Push the [
button on the unit selection screen to finish the
setting operation. " Setting" appears on the
screen for a while, then the screen returns to the
"Field setting menu" screen.
Description
– 31 –
Installation Manual
] / [
] button to select
Set
] / [
] button to select
Set" [
F2] button
<
" [
F1] button, then set
] / [
>
" [
F2] button, then set "Data"
] / [
] button.
MENU] button to set the other
Yes" [
F1] button.
No" [
No
No" [
No
Factory default
0000
Set" [
.
]
F2] button to
F2] button
CANCEL]