Top Vent - Horizontal Termination
V
Minimum
1
Elbow only
6 in.
15,2 cm
1 ft.
30,5 cm
2 ft.
61,0 cm
3 ft.
91,4 cm
4 ft.
1,22 m
5 ft.
1,52 m
V
+ H
= 30 ft. (9,14 m) Maximum
1
1
USE SLP SERIES COMPONENTS ONLY
Figure 7.4
H
Maximum
1
NOT ALLOWED
1 ft.
30,5 cm
2 ft.
61,0 cm
4 ft.
1,22 m
8 ft.
2,44 m
10 ft.
3,05 m
16 ft.
4,87 m
Example: SLP pipe 7 ft. (2,13 m) min. vertical = 11 ft. (3,35 m) max. horizontal
Heat & Glo • 350TSI-P-CEM • 2033-973 Rev. G • 4/17
H
1
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling firestops.
• ALWAYS maintain specified clearances around
venting and firestop systems.
• Install wall shield and ceiling firestops as speci-
fied.
Failure to keep insulation or other material away
from vent pipe could cause fire.