Commissioning
After installation, a 24 hours charging cycle must be completed, in order to achieve the nominal
—
autonomy.
During commissioning of the luminaire write the commissioning date on the battery.
—
When power is applied to the unit inspect that the CHARGE indicator is either blinking or steady, all other
—
indicators are OFF and that the led lamp is lit (maintained operation) or OFF (non-maintained operation)
A full duration test should be conducted after verifying that the CHARGE indicator is continuously ON. Test is
—
initiated by isolating the mains power supply. Verify that the LED lamp is lit during the test period for at least
the stated duration.
Accessories for installation
(After request)
Α-2130: Accessory for ceiling (1m)
Α-2131: Accessory for ceiling (0,5m)
Α-2132: Accessory for ceiling (0,25m)
Α-2133: Accessory for wall mounting
Α-2136: Accessory for hanging installation (2,5m)
Battery replacement
1. Disassemble the luminary.
2. Remove the battery connector and carefully remove the battery from its base.
3. Install a new battery of the same type and rating.
4. Assemble the luminary and power the device.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
B: Including remote test mode
C: Including inhibiting mode
E: With non-replacable lamp(s) and/or battery
F: Automatic test gear complying with IEC 61347-2-7 denoted EL-T
60: 1 hour duration
180: 3 hours duration
480: 8 hours duration
X 1
A B
C
E
F
1
8 0
(*) Maintained operation: The luminary lights its illumination source, when it is
powered by the mains power supply or not.
Non Maintained operation: The luminary lights its illumination source, only in
power supply's failure.
ATTENTION!!!
The light source of this luminary is not replaceable when the light source
reaches its end of life the whole luminary shall be replaced.
4
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
SUPPLY CURRENT
U-OUT
Prated
Irated
MAX OPEN CIRCUIT VOLTAGE
EMERGENCY OUTPUT FACTOR (EoFx)
WIRE CROSS SECTION
MINIMUM POWER FACTOR
BATTERY (Ni-MH)
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
BATTERY PROTECTION
MIN MAX. DISCHARGE VOLTAGE
MIN MAX. DISCHARGE CURRENT
MIN MAX. CHARGE CURRENT
TRICKLE CHARGE VOLTAGE/CURRENT
MAX CHARGE VOLTAGE
INDICATIONS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE / OUTPUT MODE
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
CONTROL GEAR MAX.TEMPERATURE: tc
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
NOMINAL POWER
CONNECTIONS
TEMPERATURE
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical
leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not
follow the technical instructions included in official documents given by Olympia Electronics or if
the buyer modifies the goods provided or has any repairs or re-setting done by a third party,
unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged
can be returned to the premises of our company for repair or replacement, as long as the
warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not
charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to
charge or not the buyer the transportation cost.
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
922502058_09_004
5
KLIN-20/ST/ADR
220-240V AC / 50-60Hz
3.9W / 4.4VA
20mA
70V
1.5W
130mA
39V DC
1h: 3.4, 3h: 1.4, 8h: 0.2
0.08mm - 1.5mm
2
2
0.87
3.6V/1.5Ah
Basic insulation
Basic insulation
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
3 - 4.5V
1h (400-690mA), 3h (190-295mA), 8h (55-95mA)
20 - 120mA
4.4V / 40mA
4.9V
LED Charge, Lamp Fault LED, Battery Fault LED / Test Button
24 hours
1h / 3h / 8h Manually Selected (Default 3h)
LED / CONSTANT CURRENT
80lm / 1h: 250lm, 3h: 77lm, 8h: 12lm
IP54
EN 60598-1, EN 60598-2-22, ΕΝ 55015,
ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
o
5 to 40 C
o
58 C at BR1
Up to 95%
PC
260 x 35 x 60 mm
420gr.
3 years (1 year for the battery)
LED Characteristics
KLIN-20/ST/ADR
Olympia Electronics S.A.
2711195
11.2-13.2V DC
0.72
Built-in main board
45 °C max. across the board
Warranty
www.olympia-electronics.com
info@olympia-electronics.gr
922502058_09_004
European
manufacturers
KLIN-20/ST/ADR
ADDRESSABLE SELF TESTING MAINTAINED
EMERGENCY LUMINAIRE
M
ΝΜ
ADR
Duration
Light output
Addres-
IP54
Maintained
Non
1h/3h/8h
250/77/12lm
maintained
sable